2016-09-19 13:30:27 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THE SEPARATION DISTANCES OF THE PROPOSED TRAILERS |
| ARE NOT INDICATED AND APPEAR TO NOT MEET THE MINIMUM |
| SEPARATION DISTANCES IN NFPA 241. THE PROPOSED |
| CONFIGURATION IS CONSIDERED A LARGE CONSTRUCTION |
| SUPPORT COMPLEX. FIRE SPRINKLER PROTECTION WOULD BE |
| REQUIRED TO REDUCE THE DISTANCES BY 75%. |
| |
| PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; |
| |
| TABLE 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE |
| REQUIRED IN EACH TRAILER. |
| 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER |
| CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH |
| AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER |
| FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS |
| HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE |
| IN ACCORDANCE WITH TABLE 4.2.1. |
| |
| 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| |
| NOTES: |
| (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY |
| STRUCTURES IS LESS THAN THE MINIMUM SEPARATION |
| DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE |
| CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING |
| WALL LENGTHS OF THE TEMPORARY STRUCTURES. |
| (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES |
| SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL |
| STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO |
| MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE |
| APPLYING THIS TABLE, IS 3600 MM (144 IN.). |
| |
| 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES, |
| ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND |
| PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE |
| AUTHORITY HAVING JURISDICTION. |
| |
| A.4.2.2 WHERE LOCATED 9M(30 FT) OR MORE FROM THE |
| STRUCTURE AND CONSTRUCTED OF COMBUSTIBLE MATERIALS, IT |
| IS RECOMMENDED THAT TEMPORARY SUPPORT BUILDINGS BE |
| DIVIDED INTO SMALL, DETACHED UNITS TO MINIMIZE FIRE |
| LOSS. LARGE CONSTRUCTION SUPPORT |
| COMPLEXES SHOULD BE PROTECTED WITH ADEQUATE FIRE |
| PROTECTION (E.G., AUTOMATIC SPRINKLERS, YARD HYDRANTS, |
| HOSE, AND EXTINGUISHERS) AS REQUIRED BY THE AUTHORITY |
| HAVING JURISDICTION. |
| |
| |
| PLEASE PROVIDE FOR THE MINIMUM SPEARATION DISTANCES OR |
| PROVIDE FIRE SPRINKLER PROTECTION IN EACH TRAILER. |
| |
| |