2016-09-15 16:25:39 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: TEMPORARY OFFICES AT MERRY PLACE |
| JOB ADDRESS: 1914 MERRY PLACE |
| DESCRIPTION: TEMPORARY STATE APPROVED MODULAR OFFICE |
| SPACE. INCLUDING PLUMB, ELECTRIC, HVAC, FOUNDATION |
| BLOCKING AND TIE-DOWN. |
| MASTER PERMIT: 16090422 |
| |
| BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| SUBMITTED CORRECTIONS. |
| 1. ELECTRICAL SUB PERMIT REQUIRED. |
| 2. YOU SHALL SUBMIT A SITE PLANS INDICATING THE |
| LOCATION OF THE ELECTRICAL POWER SOURCE WHETHER IT IS |
| FROM A UTILITY POLE OR A TRANSFORMER. MARK ON THAT THE |
| LOCATION OF THE TERMINAL RACK WITH THE METER AND |
| SERVICE DISCONNECTS. MARK THE PROPOSED ROUTE FOR THE |
| FEEDERS. |
| 3. MARK ON THE PLAN THE PROPOSED ROUTE FROM THE |
| TERMINAL RACK TO THE EXISTING SERVICE PANEL OF THE |
| UNIT. |
| 4. PROVIDE AN ELECTRICAL RISER DIAGRAM OF THE COMPLETE |
| INSTALLATION FROM THE SOURCE TO THE INDIVIDUAL UNIT. |
| INDICATE AS PART OF THE RISER THE RACEWAY AND CONDUCTOR |
| TYPES. |
| 5. FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER |
| OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM |
| OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR |
| A MAXIMUM OF 3% VOLTAGE DROP. PROVIDE LOAD CALCS FOR |
| THE SERVICE AND FEEDERS TAKING INTO ACCOUNT THE VARIOUS |
| DISTANCES FOR VOLTAGE DROP CONSIDERATIONS. |
| 6. NEC 110.27(B): IN LOCATIONS WHERE ELECTRICAL |
| EQUIPMENT IS LIKELY TO BE EXPOSED TO PHYSICAL DAMAGE, |
| ENCLOSURES OR GUARDS SHALL BE ARRANGED AND OF SUCH |
| STRENGTH AS TO PREVENT SUCH DAMAGE. BOLLARDS MAY BE |
| NECESSARY. |
| 7. NEC 110.16: ELECTRICAL EQUIPMENT IN OTHER THAN |
| DWELLING UNITS LIKELY TO REQUIRE SERVICE WHILE |
| ENERGIZED SHALL BE FIELD MARKED TO WARN AGAINST |
| POTENTIAL ARC-FAULT HAZARDS. |
| 8. NEC 110.24: THE MAXIMUM AVAILABLE FAULT CURRENT |
| SHALL BE DURABLY MARKED AND DATED ON ALL NON-DWELLING |
| ELECTRICAL APPARATUS. |
| 9. 1006.1 ILLUMINATION REQUIRED. THE MEANS OF EGRESS, |
| INCLUDING THE EXIT DISCHARGE, SHALL BE ILLUMINATED AT |
| ALL TIMES THE BUILDING SPACE SERVED BY THE MEANS OF |
| EGRESS IS OCCUPIED. |
| 10. ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION |
| UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL |
| INSPECTOR. NO SITE TUBES WILL BE ACCEPTED |
| |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |