Plan Review Notes
Plan Review Notes For Permit 16090422
Permit Number 16090422
Review Stop E
Sequence Number 1
Notes
Date Text
2016-09-15 16:25:39ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME: TEMPORARY OFFICES AT MERRY PLACE
 JOB ADDRESS: 1914 MERRY PLACE
 DESCRIPTION: TEMPORARY STATE APPROVED MODULAR OFFICE
 SPACE. INCLUDING PLUMB, ELECTRIC, HVAC, FOUNDATION
 BLOCKING AND TIE-DOWN.
 MASTER PERMIT: 16090422
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
 1. ELECTRICAL SUB PERMIT REQUIRED.
 2. YOU SHALL SUBMIT A SITE PLANS INDICATING THE
 LOCATION OF THE ELECTRICAL POWER SOURCE WHETHER IT IS
 FROM A UTILITY POLE OR A TRANSFORMER. MARK ON THAT THE
 LOCATION OF THE TERMINAL RACK WITH THE METER AND
 SERVICE DISCONNECTS. MARK THE PROPOSED ROUTE FOR THE
 FEEDERS.
 3. MARK ON THE PLAN THE PROPOSED ROUTE FROM THE
 TERMINAL RACK TO THE EXISTING SERVICE PANEL OF THE
 UNIT.
 4. PROVIDE AN ELECTRICAL RISER DIAGRAM OF THE COMPLETE
 INSTALLATION FROM THE SOURCE TO THE INDIVIDUAL UNIT.
 INDICATE AS PART OF THE RISER THE RACEWAY AND CONDUCTOR
 TYPES.
 5. FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER
 OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
 OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR
 A MAXIMUM OF 3% VOLTAGE DROP. PROVIDE LOAD CALCS FOR
 THE SERVICE AND FEEDERS TAKING INTO ACCOUNT THE VARIOUS
 DISTANCES FOR VOLTAGE DROP CONSIDERATIONS.
 6. NEC 110.27(B): IN LOCATIONS WHERE ELECTRICAL
 EQUIPMENT IS LIKELY TO BE EXPOSED TO PHYSICAL DAMAGE,
 ENCLOSURES OR GUARDS SHALL BE ARRANGED AND OF SUCH
 STRENGTH AS TO PREVENT SUCH DAMAGE. BOLLARDS MAY BE
 NECESSARY.
 7. NEC 110.16: ELECTRICAL EQUIPMENT IN OTHER THAN
 DWELLING UNITS LIKELY TO REQUIRE SERVICE WHILE
 ENERGIZED SHALL BE FIELD MARKED TO WARN AGAINST
 POTENTIAL ARC-FAULT HAZARDS.
 8. NEC 110.24: THE MAXIMUM AVAILABLE FAULT CURRENT
 SHALL BE DURABLY MARKED AND DATED ON ALL NON-DWELLING
 ELECTRICAL APPARATUS.
 9. 1006.1 ILLUMINATION REQUIRED. THE MEANS OF EGRESS,
 INCLUDING THE EXIT DISCHARGE, SHALL BE ILLUMINATED AT
 ALL TIMES THE BUILDING SPACE SERVED BY THE MEANS OF
 EGRESS IS OCCUPIED.
 10. ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION
 UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL
 INSPECTOR. NO SITE TUBES WILL BE ACCEPTED
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  