2016-09-19 13:23:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SEPARATION DISTANCES OF THE PROPOSED TRAILERS
 ARE NOT INDICATED AND APPEAR TO NOT MEET THE MINIMUM
 SEPARATION DISTANCES IN NFPA 241. THE PROPOSED
 CONFIGURATION IS CONSIDERED A LARGE CONSTRUCTION
 SUPPORT COMPLEX. FIRE SPRINKLER PROTECTION WOULD BE
 REQUIRED TO REDUCE THE DISTANCES BY 75%.
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS;
  
 TABLE 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 A.4.2.2 WHERE LOCATED 9M(30 FT) OR MORE FROM THE
 STRUCTURE AND CONSTRUCTED OF COMBUSTIBLE MATERIALS, IT
 IS RECOMMENDED THAT TEMPORARY SUPPORT BUILDINGS BE
 DIVIDED INTO SMALL, DETACHED UNITS TO MINIMIZE FIRE
 LOSS. LARGE CONSTRUCTION SUPPORT
 COMPLEXES SHOULD BE PROTECTED WITH ADEQUATE FIRE
 PROTECTION (E.G., AUTOMATIC SPRINKLERS, YARD HYDRANTS,
 HOSE, AND EXTINGUISHERS) AS REQUIRED BY THE AUTHORITY
 HAVING JURISDICTION.
  
  
 PLEASE PROVIDE FOR THE MINIMUM SPEARATION DISTANCES OR
 PROVIDE FIRE SPRINKLER PROTECTION IN EACH TRAILER.
  
  