2016-11-02 16:00:34REVISION 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] A GROUNDED CONDUCTOR SHALL NOT BE CONNECTED TO
 NORMALLY NON-CURRENT-CARRYING METAL PARTS OF EQUIPMENT,
 TO EQUIPMENT GROUNDING CONDUCTOR(S), OR BE RECONNECTED
 TO GROUND ON THE LOAD SIDE OF THE SERVICE DISCONNECTING
 MEANS. PLEASE SEPERATE NUETRAL FROM GROUND AT PANEL "C"
 AS PER NEC 250.24(A)(5).