Plan Review Notes For Permit 16090394 |
Permit Number |
16090394 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-10-12 08:59:20 | 1) SHT. P2.1 - THERE IS A DRYWELL THAT APPEARS TO BE | | LOCATED UNDER AN EXTERIOR RAMP. CLARIFY. | | 2) SHOW THE FUTURE WATER LINE TO THE SECOND FLOOR ON | | THE WATER RISER. | | 3) THE TEMPERATURE OF THE HOT WATER FROM THE | | INSTANTANEOUS WATER HEATER SHALL BE CONTROLLED BY A | | TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070 | | AND SHALL LIMIT THE TEMPERATURE TO 110 DEGREES. FPC | | 607.1.2. | | 4) SHT. P5.1 - SUBMIT AN EXPANDED SANITARY RISER | | DIAGRAM FOR REVIEW. IT APPEARS AS THOUGH THE DRINKING | | FOUNTAIN MAY BE INSTALLED ON A WET VENT. | | 5) THE SINK IN THE WORK ROOM APPEARS TO BE INSTALLED ON | | A HORIZONTAL WET VENT. ONLY THE FIXTURES LOCATED IN A | | BATHROOM GROUP SHALL DISCHARGE INTO A HORIZONTAL WET | | VENT PER FPC SEC.912.1. REFER TO THE DEFINITION OF | | BATHROOM GROUP IN FPC SEC. 202. | | 6) THE RISER DIAGRAM SHOWS A FLAT, DRY VENT FOR THE TWO | | FLOOR DRAINS IN THE PAPER MAKING AREA. THE VENT SHALL | | CONNECT TO THE HORIZONTAL DRAIN ABOVE THE CENTERLINE OF | | THE HORIZONTAL DRAIN PIPE. FPC SEC.905.3. | | 7) THE WASHING MACHINE SHALL BE INSTALLED ON A 3 INCH | | STACK. FPC SEC. 406.2. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|