2016-10-12 08:59:201) SHT. P2.1 - THERE IS A DRYWELL THAT APPEARS TO BE
 LOCATED UNDER AN EXTERIOR RAMP. CLARIFY.
 2) SHOW THE FUTURE WATER LINE TO THE SECOND FLOOR ON
 THE WATER RISER.
 3) THE TEMPERATURE OF THE HOT WATER FROM THE
 INSTANTANEOUS WATER HEATER SHALL BE CONTROLLED BY A
 TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070
 AND SHALL LIMIT THE TEMPERATURE TO 110 DEGREES. FPC
 607.1.2.
 4) SHT. P5.1 - SUBMIT AN EXPANDED SANITARY RISER
 DIAGRAM FOR REVIEW. IT APPEARS AS THOUGH THE DRINKING
 FOUNTAIN MAY BE INSTALLED ON A WET VENT.
 5) THE SINK IN THE WORK ROOM APPEARS TO BE INSTALLED ON
 A HORIZONTAL WET VENT. ONLY THE FIXTURES LOCATED IN A
 BATHROOM GROUP SHALL DISCHARGE INTO A HORIZONTAL WET
 VENT PER FPC SEC.912.1. REFER TO THE DEFINITION OF
 BATHROOM GROUP IN FPC SEC. 202.
 6) THE RISER DIAGRAM SHOWS A FLAT, DRY VENT FOR THE TWO
 FLOOR DRAINS IN THE PAPER MAKING AREA. THE VENT SHALL
 CONNECT TO THE HORIZONTAL DRAIN ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE. FPC SEC.905.3.
 7) THE WASHING MACHINE SHALL BE INSTALLED ON A 3 INCH
 STACK. FPC SEC. 406.2.
  