2016-09-27 18:32:18ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 4912 S. DIXIE HWY.
 DESCRIPTION: REVISION TO MASTER.
 MASTER PERMIT: 15090611
 REVISION NUMBER: 16090394
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. SHEET E0.1: CORRECT NOTE PART I, C1 TO READY NEC
 2011.
 2. SHEET E2.1: FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL:
 DAYLIGHT ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN
 THE DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF
 GENERAL AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE
 WITH EITHER SECTION C405.2.2.3.1 OR SECTION
 C405.2.2.3.2.
 3. SHEET E2.1: EXIT LIGHT MISSING AT THE WEST DOOR.
 4. SHEET E2.2: FBC-R404.1 LIGHTING EQUIPMENT
 (MANDATORY). A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS.
 5. SHEET E3.1: NEC 210.62 SHOW WINDOWS. AT LEAST ONE
 RECEPTACLE OUTLET SHALL BE INSTALLED WITHIN 18? OF THE
 TOP OF A SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR
 PORTION THEREOF AREA MEASURED HORIZONTALLY.
 6. SHEET E3.2: IF ROOM 200 (KITCHEN) IS TO BE A KITCHEN
 AS PART OF THIS PERMIT, PROPER OUTLET PLACEMENT AND
 SPACING WILL BE REQUIRED ON DRAWINGS. IF IT IS NOT PART
 OF THIS SCOPE, A NOTE WILL BE ADDED TO EXCLUDE THE
 KITCHEN FROM THIS PERMIT.
 7. SHEET E6.1: FBC-ER3609.3 NEC 250.94 BONDING FOR
 OTHER SYSTEMS. THE INTER-SYSTEM BONDING TERMINAL
 PRESCRIBED SHALL BE INSTALLED.
 8. SHEET E6.1: FBC-RE3601.6.2 NEC 240.24 LOCATION IN OR
 ON PREMISES. (A) & (B) PANELS SHALL BE LOCATED SUCH
 THAT OVER CURRENT DEVICES ARE ACCESSIBLE AND THAT
 OCCUPANTS SHALL HAVE ACCESS TO OCP DEVICES. THIS
 APPLIES TO PANEL C WITH MDP NOT ACCESSIBLE.
 9. SHEET E6.1: YOU SHALL INCLUDE WITH THE RISER DIAGRAM
 COMPLETE LOAD CALCS AS REQUIRED BY CODE.
 10. FBC-R303.9 REQUIRED HEATING. WHEN THE WINTER DESIGN
 TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C),
 EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING
 FACILITIES CAPABLE OF MAINTAINING A MINIMUM ROOM
 TEMPERATURE OF 68?F (20?C) AT A POINT 3 FEET (914 MM)
 ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS
 IN ALL HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE
 INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746