Plan Review Notes For Permit 16090364 |
Permit Number |
16090364 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-11-06 14:43:42 | 11/6/17 PLUMBING 3RD REVIEW**DENIED** | | | | THESE COMMENTS FROM THE 2ND REVIEW HAVE NOT BEEN | | ADDRESSED: IT IS RECOMMENDED YOU CONTACT THE PLAN | | REVIEW TO REVIEW COMMENTS. | | | | 1) SUBMIT FACTORY SIZING CALCULATIONS SHOWING HOW YOU | | DETERMINED THE GB-35 WAS SIZED FOR THIS APPLICATION. | | FBC-P 1003.2 | | | | 2) THE MIN SIZE FOR THE REQUIRED TEST PORT IS 4".TTHE | | SEWER LINE CAN NOT THEN BE REDUCED TO 2" .FBC-P 704.2 | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] | | |
|