Plan Review Notes
Plan Review Notes For Permit 16090364
Permit Number 16090364
Review Stop P
Sequence Number 3
Notes
Date Text
2017-11-06 14:43:4211/6/17 PLUMBING 3RD REVIEW**DENIED**
  
 THESE COMMENTS FROM THE 2ND REVIEW HAVE NOT BEEN
 ADDRESSED: IT IS RECOMMENDED YOU CONTACT THE PLAN
 REVIEW TO REVIEW COMMENTS.
  
 1) SUBMIT FACTORY SIZING CALCULATIONS SHOWING HOW YOU
 DETERMINED THE GB-35 WAS SIZED FOR THIS APPLICATION.
 FBC-P 1003.2
  
 2) THE MIN SIZE FOR THE REQUIRED TEST PORT IS 4".TTHE
 SEWER LINE CAN NOT THEN BE REDUCED TO 2" .FBC-P 704.2
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  