2016-09-12 11:29:33PERMIT # 16090325
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 2) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 3) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
 (TENT BEING USED IS 2,400 SQ. FT.)
  
 4) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 5) PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE
 CANOPY MATERIAL.
  
 6) GENERATORS AND OTHER INTERNAL COMBUSTION POWER
 SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5
 FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
 7) ALL ELECTRICAL CORDS SHALL BE IN GOOD CONDITION AND
 NOT CONTAIN SPLICING, EXPOSED WIRING, PIGTAILED
 CONNECTIONS, ETC.
  
  