Plan Review Notes For Permit 16090325 |
Permit Number |
16090325 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-09-12 11:29:33 | PERMIT # 16090325 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | APPROVED WITH COMMENTS: | | | | 1) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | 2) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | BUILDING STRUCTURES. | | | | 3) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | (TENT BEING USED IS 2,400 SQ. FT.) | | | | 4) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | LOCATIONS. | | | | 5) PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE | | CANOPY MATERIAL. | | | | 6) GENERATORS AND OTHER INTERNAL COMBUSTION POWER | | SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 | | FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR | | ENCLOSURE. | | | | 7) ALL ELECTRICAL CORDS SHALL BE IN GOOD CONDITION AND | | NOT CONTAIN SPLICING, EXPOSED WIRING, PIGTAILED | | CONNECTIONS, ETC. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 644-7326 | | |
|