Plan Review Notes For Permit 16090308 |
Permit Number |
16090308 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-09-16 11:52:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET 1 OF 2 - IN THE UNDERGROUND GENERAL NOTES | | SECTION THERE IS AN INDICATION THAT IT IS TO BE DONE BY | | A LICENSED FIRE SPRINKLER CONTRACTOR. | | | | THE UNDERGROUND SHALL PROVIDE THE APPLICABLE STATE | | LICENSE PER FLORIDA STATUTUE 633.102 | | | | | | | | 2) SHEET 1 OF 2 - UNDERGROUND PIPE SPEC SHEETS WERE NOT | | PROVIDED. | | | | PLEASE PROVIDE THE UNDERGROUND PIPE MANUFACTURES | | SPECIFICATION SHEETS. | | | | | | | | 3) NO HYDRALIC CALCULATIONS ARE PROVIDED. | | | | | | PLEASE PROVIDE HYDRALIC CALCULATIONS PER NFPA 13, | | CHAPTER 22 PLANS AND CALCULATIONS. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | | | | | | | | | | | |
|