Plan Review Notes
Plan Review Notes For Permit 16090308
Permit Number 16090308
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-09-16 11:52:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 1 OF 2 - IN THE UNDERGROUND GENERAL NOTES
 SECTION THERE IS AN INDICATION THAT IT IS TO BE DONE BY
 A LICENSED FIRE SPRINKLER CONTRACTOR.
  
 THE UNDERGROUND SHALL PROVIDE THE APPLICABLE STATE
 LICENSE PER FLORIDA STATUTUE 633.102
  
  
  
 2) SHEET 1 OF 2 - UNDERGROUND PIPE SPEC SHEETS WERE NOT
 PROVIDED.
  
 PLEASE PROVIDE THE UNDERGROUND PIPE MANUFACTURES
 SPECIFICATION SHEETS.
  
  
  
 3) NO HYDRALIC CALCULATIONS ARE PROVIDED.
  
  
 PLEASE PROVIDE HYDRALIC CALCULATIONS PER NFPA 13,
 CHAPTER 22 PLANS AND CALCULATIONS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
  