2016-09-09 08:12:55 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16090263 |
| ADD: 1731 UPLAND RD. |
| CONT: ROOFPRO |
| TEL: 561-249-0247 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SEPT. 09/2016 |
| ACTION: DENIED |
| |
| 1) THE PRODUCT APPROVAL SUBMITTED FL654-R19 A TRINTY |
| /ERD EVALUATION REPORT WAS SUBMITTED, SHEET 26 OF 45 |
| WAS SELECTED AND SYSTEM SC-26 WAS HIGHLIGHTED WITH |
| HIGHLIGHTED RECTANGLE WITH A -52.5 POUNDS PER SQUARE |
| FOOT. PAGE 4 OF 5 LIMITATIONS SECTION 5.7 DOES ALLOW |
| FOR ENHANCED FASTENING BY A QUALIFIED DESIGN |
| PROFESSIONAL, COMMON METHODS USED ARE RAS 117 AND |
| FMLPDS 1-29. |
| 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| FASTENING |
| REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT |
| EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE |
| WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE |
| OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE |
| SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION |
| DOCUMENTS. |
| |