2016-09-16 10:03:48INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
  
 1-PLEASE NOTE THAT ALL CIRCUITS? DESIGNATION AT THE
 PANELBOARDS MUST INDICATE WHAT AREA SPECIFICALLY OF THE
 HOUSE IT?S SERVICING. GENERAL LIGHTING DOES NOT MEET
 THESE REQUIREMENTS. EXAMPLE, LABEL BEDROOM 1, BEDROOM 2
 ETC.?NEC 408.4 FIELD ID REQUIRED. FBC 107.3.5
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II