2016-09-30 15:28:371ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT S-1 THE MASTER-BATH TUB AND BIDET ARE MISSING
 FROM TH RISER DIAGRAM AND FLAT FLOOR PLAN ALL FIXTURES
 SHALL BE SHOWN ON PLANS. PER WPB AMEND. TO FBC 107.2.1
  
 2. SHT. S-1 THE WAT THE MASTER BATH TOILET IS VENTED ON
 THE RISER IT WILL HAVE A VENT IN THE MIDDLE OF THE
 FLOOR , THE VENT FOR THE LAVATORY CAN SERVE THE
 BATHROOM GROUP PROVIDE ALL THE FIXTURES ARE CONNECTED
 ON THE SAME BRANCH DRAIN .
 PER FBC RES P3108.1
  
 3. THE KITCHEN, LAUNDRY AND WET BAR OFF DINNING ROOM
 SHALL ALL CONNECT TO BUILDING DRAIN DOWN STREAM OF
 POWDER ROOM BATHROOM GROUP. PER PER FBC RES P3108.1
  
 4. THE RISER DIAGRAM DOES NOT MATCH FLAT FLOOR PLAN
 PLEASE CLARIFY. PER WPB AMEND. TO FBC 107.2.1
  
 5. PLEASE PROVIDE A WATER RISER DIAGRAM/ PER WPB AMEND
 TO FBC 107.3.5.3
  
  
  
  