Plan Review Notes For Permit 16090221 |
Permit Number |
16090221 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-09-30 15:28:37 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1. SHT S-1 THE MASTER-BATH TUB AND BIDET ARE MISSING | | FROM TH RISER DIAGRAM AND FLAT FLOOR PLAN ALL FIXTURES | | SHALL BE SHOWN ON PLANS. PER WPB AMEND. TO FBC 107.2.1 | | | | 2. SHT. S-1 THE WAT THE MASTER BATH TOILET IS VENTED ON | | THE RISER IT WILL HAVE A VENT IN THE MIDDLE OF THE | | FLOOR , THE VENT FOR THE LAVATORY CAN SERVE THE | | BATHROOM GROUP PROVIDE ALL THE FIXTURES ARE CONNECTED | | ON THE SAME BRANCH DRAIN . | | PER FBC RES P3108.1 | | | | 3. THE KITCHEN, LAUNDRY AND WET BAR OFF DINNING ROOM | | SHALL ALL CONNECT TO BUILDING DRAIN DOWN STREAM OF | | POWDER ROOM BATHROOM GROUP. PER PER FBC RES P3108.1 | | | | 4. THE RISER DIAGRAM DOES NOT MATCH FLAT FLOOR PLAN | | PLEASE CLARIFY. PER WPB AMEND. TO FBC 107.2.1 | | | | 5. PLEASE PROVIDE A WATER RISER DIAGRAM/ PER WPB AMEND | | TO FBC 107.3.5.3 | | | | | | | | |
|