2016-09-16 10:00:47 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA RES BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 |
| COMMENTS: |
| |
| 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND |
| LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC |
| RATINGS. FBC 107.3.5 |
| 2. REVISE SERVICE CONDUCTORS, UNDERSIZED FOR A 400AMP |
| SERVICE. FBC RES E3603 |
| 3. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS |
| FOR LOW VOLTAGE SYSTEMS AND POOL. FBC 107.3.5 |
| 4. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE |
| PER FBC RES E3609.3 |
| 5. GROUNDING ELECTRODE CONDUCTOR IS UNDERSIZED FOR |
| 400AMP SERVICE. #2 REQUIRED PER NEC 250.66. FBC RES |
| E3603 |
| 6. PLEASE SHOW THE FEEDER CONDUCTOR SIZES AND EQUIPMENT |
| GROUNDING CONDUCTOR REQUIRED WITH THESE FEEDERS. FBC |
| 107.3.5 |
| 7. PLEASE NOTE THAT THE RISER DIAGRAM DOES NOT MATCH |
| THE FLOOR PLAN LAYOUT OF PANEL LOCATION. IF 400A PANEL |
| IS LOCATED IN GARAGE SHOWN AS A 200AMP PANEL, CORRELATE |
| AND CORRECT. IF THERE IS A MAIN CB, AS SHOWN OUTSIDE |
| PLEASE SHOW ON RISER DIAGRAM. LABEL EQUIPMENT AS RATED |
| FOR SERVICE ENTRANCE AND PROPER NEMA 3R RATING. FBC |
| 107.3.5 |
| 8. CLARIFY BUS RATING FOR PANEL P SHOWN AT 60AMP; IS IT |
| 100 AMP POOL PANEL? TYPICAL. FBC 107.3.5 |
| 9. AT THE RISER DIAGRAM SHOW CONDUCTOR SIZE FOR PANEL |
| B. FBC RES E3603 |
| 10. SHOW EXTERIOR RECEPTACLE AT REAR PROTECTED BY GFCI |
| DEVICE. FBC RES E3902.3 |
| 11. RECEPTACLE AT WALL SPACE IN KITCHEN AREA WITHIN 6FT |
| OF SINK TO BE LABELED AS GFCI PROTECTED. FBC RES |
| E3902.7 |
| 12. RECEPTACLE AT WALL SPACE IN WET BAR AREA WITHIN 6FT |
| OF SINK TO BE LABELED AS GFCI PROTECTED. FBC RES |
| E3902.7 |
| 13. SHOW JACUZZI AND GARAGE DOOR OPENER DEVICES TO BE |
| PROTECTED BY GFCI BREAKER TO BE READILY ACCESSIBLE. A |
| NOTE WILL SUFFICE. |
| 14. PLEASE NOTE THAT ALL CIRCUITS? DESIGNATION AT THE |
| PANELBOARDS MUST INDICATE WHAT AREA SPECIFICALLY OF THE |
| HOUSE IT?S SERVICING. GENERAL LIGHTING DOES NOT MEET |
| THESE REQUIREMENTS. EXAMPLE, LABEL BEDROOM 1, BEDROOM 2 |
| ETC.?NEC 408.4 FIELD ID REQUIRED. FBC 107.3.5 |
| 15. PROVIDE A NOTE TO INDICATE REQUIRED TAMPER |
| RESISTANT RECEPTACLE THROUGHOUT. FBC RES E4002.14 |
| 16. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO |
| INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS. |
| 17. PLEASE SHOW ON PANELBOARD 20A CIRCUITS REQUIRED FOR |
| DINING ROOM RECEPTACLES AND BATHROOM RECEPTACLES. FBC |
| RES E3703.2 AND 4 |
| 18. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY |
| QUESTIONS OR CONCERNS. |
| |