2016-09-16 10:00:47INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND
 LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC
 RATINGS. FBC 107.3.5
 2. REVISE SERVICE CONDUCTORS, UNDERSIZED FOR A 400AMP
 SERVICE. FBC RES E3603
 3. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS AND POOL. FBC 107.3.5
 4. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3
 5. GROUNDING ELECTRODE CONDUCTOR IS UNDERSIZED FOR
 400AMP SERVICE. #2 REQUIRED PER NEC 250.66. FBC RES
 E3603
 6. PLEASE SHOW THE FEEDER CONDUCTOR SIZES AND EQUIPMENT
 GROUNDING CONDUCTOR REQUIRED WITH THESE FEEDERS. FBC
 107.3.5
 7. PLEASE NOTE THAT THE RISER DIAGRAM DOES NOT MATCH
 THE FLOOR PLAN LAYOUT OF PANEL LOCATION. IF 400A PANEL
 IS LOCATED IN GARAGE SHOWN AS A 200AMP PANEL, CORRELATE
 AND CORRECT. IF THERE IS A MAIN CB, AS SHOWN OUTSIDE
 PLEASE SHOW ON RISER DIAGRAM. LABEL EQUIPMENT AS RATED
 FOR SERVICE ENTRANCE AND PROPER NEMA 3R RATING. FBC
 107.3.5
 8. CLARIFY BUS RATING FOR PANEL P SHOWN AT 60AMP; IS IT
 100 AMP POOL PANEL? TYPICAL. FBC 107.3.5
 9. AT THE RISER DIAGRAM SHOW CONDUCTOR SIZE FOR PANEL
 B. FBC RES E3603
 10. SHOW EXTERIOR RECEPTACLE AT REAR PROTECTED BY GFCI
 DEVICE. FBC RES E3902.3
 11. RECEPTACLE AT WALL SPACE IN KITCHEN AREA WITHIN 6FT
 OF SINK TO BE LABELED AS GFCI PROTECTED. FBC RES
 E3902.7
 12. RECEPTACLE AT WALL SPACE IN WET BAR AREA WITHIN 6FT
 OF SINK TO BE LABELED AS GFCI PROTECTED. FBC RES
 E3902.7
 13. SHOW JACUZZI AND GARAGE DOOR OPENER DEVICES TO BE
 PROTECTED BY GFCI BREAKER TO BE READILY ACCESSIBLE. A
 NOTE WILL SUFFICE.
 14. PLEASE NOTE THAT ALL CIRCUITS? DESIGNATION AT THE
 PANELBOARDS MUST INDICATE WHAT AREA SPECIFICALLY OF THE
 HOUSE IT?S SERVICING. GENERAL LIGHTING DOES NOT MEET
 THESE REQUIREMENTS. EXAMPLE, LABEL BEDROOM 1, BEDROOM 2
 ETC.?NEC 408.4 FIELD ID REQUIRED. FBC 107.3.5
 15. PROVIDE A NOTE TO INDICATE REQUIRED TAMPER
 RESISTANT RECEPTACLE THROUGHOUT. FBC RES E4002.14
 16. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO
 INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS.
 17. PLEASE SHOW ON PANELBOARD 20A CIRCUITS REQUIRED FOR
 DINING ROOM RECEPTACLES AND BATHROOM RECEPTACLES. FBC
 RES E3703.2 AND 4
 18. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  