Plan Review Notes For Permit 16090221 |
Permit Number |
16090221 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-10-04 15:12:57 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SHOW COMPLIANCE WITH FBC-R 310.1 EMERGENCY ESCAPE | | AND RESCUE WINDOWS IN BEDROOM NUMBER 3. | | | | 2) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED | | TO INSTALL THE ROOF TILE. IF AN ADHESIVE WILL BE USED, | | SUBMIT TWO COPIES OF THE PRODUCT APPROVAL FOR THE | | ADHESIVE. FBC 107.2.1 & FAC RULE 9N-3. | | | | 3) THE ENERGY CALCULATIONS FOR THE MAIN HOUSE LISTS THE | | NUMBER OF OCCUPANTS AS 6 IN THE MASTER BEDROOM AREA AND | | 10 IN THE MAIN AREA FOR A TOTAL OF 16. A FOUR BEDROOM | | HOUSE WILL TYPICALLY HAVE 8 OCCUPANTS. FBC ENERGY | | CONSERVATION R405 | | | | 4) THE ENERGY CALCULATION FORMS FOR THE GUEST HOUSE | | LISTS THE HEAT SYSTEM AS 21.3 KBTU/HR (6.2 KW) AND THE | | EQUIPMENT SCHEDULE ON THE HVAC PLANS SPECIFIES 8 KW FOR | | THE HEAT. PLEASE CLARIFY. | | | | 5) THIS PROPERTY IS ZONED SF7, THE GUEST HOUSE MAY NOT | | BE ALLOWED TO HAVE A FULL KITCHEN AS INDICATED ON THE | | PLANS. CHECK WITH THE WEST PALM BEACH ZONING DIVISION. |
|