2016-10-04 15:12:57PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH FBC-R 310.1 EMERGENCY ESCAPE
 AND RESCUE WINDOWS IN BEDROOM NUMBER 3.
  
 2) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE ROOF TILE. IF AN ADHESIVE WILL BE USED,
 SUBMIT TWO COPIES OF THE PRODUCT APPROVAL FOR THE
 ADHESIVE. FBC 107.2.1 & FAC RULE 9N-3.
  
 3) THE ENERGY CALCULATIONS FOR THE MAIN HOUSE LISTS THE
 NUMBER OF OCCUPANTS AS 6 IN THE MASTER BEDROOM AREA AND
 10 IN THE MAIN AREA FOR A TOTAL OF 16. A FOUR BEDROOM
 HOUSE WILL TYPICALLY HAVE 8 OCCUPANTS. FBC ENERGY
 CONSERVATION R405
  
 4) THE ENERGY CALCULATION FORMS FOR THE GUEST HOUSE
 LISTS THE HEAT SYSTEM AS 21.3 KBTU/HR (6.2 KW) AND THE
 EQUIPMENT SCHEDULE ON THE HVAC PLANS SPECIFIES 8 KW FOR
 THE HEAT. PLEASE CLARIFY.
  
 5) THIS PROPERTY IS ZONED SF7, THE GUEST HOUSE MAY NOT
 BE ALLOWED TO HAVE A FULL KITCHEN AS INDICATED ON THE
 PLANS. CHECK WITH THE WEST PALM BEACH ZONING DIVISION.