Plan Review Notes
Plan Review Notes For Permit 16090175
Permit Number 16090175
Review Stop G
Sequence Number 2
Notes
Date Text
2016-09-17 03:36:451) THE PLAN STATES A 2 PSI SYSTEM BUT THE TABLE THAT
 HAS BEEN SUBMITTED IS FOR A 10 PSI SYSTEM. CLARIFY.
 SUBMIT 2 COPIES OF THE CORRECT SIZING TABLE BEING USED
 FOR THIS INSTALLATION. WPB AMEND. TO FBC SEC. 107.2.1,
 FLOEIDA FUEL GAS CODE SEC.402.3.
 2) SUBMIT TWO COPIES OF ALL DOCUMENTS. ONLY ONE COPY
 HAS BEEN SUBMITTED FOR THE TANK SPECS, ANCHORING SPECS
 AND THE SIZING TABLE. WPB AMEND. TO FBC SEC. 107.1.
 3) SUBMIT COMPLETE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATIONN MANUAL FOR REVIEW. THE
 GENERATOR SHALL BE UL 2200 LISTED AND BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37. 2014 FBC-FUEL GAS SEC.616.1.
 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  