2016-09-12 10:01:13 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER ? PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1. RESIDENT INSPECTOR AGREEMENT |
| A. SUBMITTAL TO BE IN TRIPLICATE. |
| B. JOB INSPECTOR LEFT BLANK. IF NO JOB INSPECTOR IS TO |
| BE USED MARK N/A. IF JOB INSPECTOR IS TO BE USED, |
| COMPLETE SECTION AND NOTARIZE. PROVIDE RESUME OF |
| INSPECTOR. |
| C. PROVIDE RESUME OF SPECIAL INSPECTOR. |
| D. ENTER NAME OF CERTIFIED INSPECTION COMPANY AND HAVE |
| NOTARIZED. |
| E. ARCHITECT OR ENGINEER OF RECORD TO SIGN AND SEAL |
| WHERE INDICATED. |
| 2. PROVIDE SITE PLAN INDICATING STAGING AREA. |
| 3. PROVIDE PLAN WITH ELEVATIONS IDENTIFYING LOCATION |
| AND QUANITY OF WORK. |
| 4. CANNOT VERIFY VALUE AT THIS TIME. ADDITIONAL |
| INFORMATION REQUIRED. |
| |
| |
| RESIDENT INSPECTOR |
| |
| CITY OF WEST PALM BEACH |
| LOCAL AMENDMENTS TO THE |
| FLORIDA BUILDING CODE (FBC) 2010 |
| CHAPTER 1 ADMINISTRATION |
| |
| 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING |
| OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE |
| INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT |
| REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION |
| SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS |
| SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A |
| CERTIFICATE CALLED FOR BY ANY PROVISION OF THE |
| TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS |
| UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A |
| RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| SERVICE IN THE FOLLOWING INSTANCES: |
| |
| SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| THE RESIDENT INSPECTOR. |
| |
| THE CONTRACTOR SHALL PRODUCE A JOB SUMMARY OR HISTORY |
| FOR THIS TYPE OF CONSTRUCTION. |
| |
| PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTION LINE @ (561) 805-6700 FOR ALL |
| BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. WITHOUT THIS, THE PERMIT EXPIRES IN 6 |
| MONTHS WHICH WILL RESULT IN ?ABANDONMENT OF JOB, NO |
| INSPECTION ACTIVITY?. THE PERMIT WILL BECOME EXPIRED. |
| |
| PLEASE PROVIDE A SITE PLAN SHOWING THE PROPERTY LINES, |
| CONSTRUCTION AREAS, STAGING AREAS, HOW THE OCCUPANTS OF |
| THE BUILDING WILL BE SAFE GUARDED DURING THEIR ENTRY |
| AND EXIT OF THE BUILDING. SHOW COMPLIANCE WITH 2014 FBC |
| 3306.7 ? COVERED WALKWAYS, INCLUDING LIGHTING FOR THE |
| EXIT DISCHARGE. 2014 FBC 3310.2 ? MAINTENANCE OF MEANS |
| OF EGRESS. REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED |
| AT ALL TIMES DURING CONSTRUCTION, DEMOLITION, |
| REMODELING OR ALTERATIONS AND ADDITIONS TO ANY |
| BUILDING. |
| |
| IF SCAFFOLDING EXTENDS BEYOND THE PRIVATE PROPERTY AND |
| ONTO CITY RIGHT OF WAY, ENGINEERING WILL REQUIRE RIGHT |
| OF WAY PERMITS. PLEASE CONTACT MANNY GONZALEZ AT THE |
| ENGINEERING DEPARTMENT ? (561) 494-1085. |
| |
| IF SCAFFOLDING IS TO BE USED FOR THE HEIGHT OF THE |
| BUILDING, PLEASE PROVIDE HOW THE SCAFFOLDING WILL BE |
| BUILT AS WELL AS HOW THE SCAFFOLDING WILL BE ANCHORED |
| TO RESIST LATERAL WIND LOADING. THERE APPEARS SAND |
| BLASTING WILL ALSO BE AN ELEMENT OF THE OPERATION, HOW |
| WILL THE SANDBLASTING BE CONTAINED, WILL THERE BE WIND |
| SCREENS, IF SO PLEASE PROVIDE WHAT ELEMENTS WILL BE |
| INTRODUCED TO KEEP THE SCAFFOLDING FROM MOVING WITH THE |
| LATERAL EFFECT OF WIND ON THE WIND SCREENS. AT WHAT |
| SAFETY FACTOR ARE THESE ELEMENTS FACTORED? 107.2.1.3 |
| ADDITIONAL INFORMATION. 2014 FBC 3302.1 & 3306.1. |
| |
| PROVIDE COMPLIANCE WITH FBC 3309.1 WHERE REQUIRED. ALL |
| STRUCTURES UNDER CONSTRUCTION, ALTERATION OR DEMOLITION |
| SHALL BE PROVIDED WITH NO FEWER THAN ONE APPROVED |
| PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH SECTION |
| 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD AS |
| FOLLOWS: |
| |
| THE SPECIAL INSPECTOR, UPON COMPLETION OF THE BUILDING |
| AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| OR COMPLETION, FILE A SIGNED AND SEALED STATEMENT WITH |
| THE ENFORCEMENT AGENCY IN SUBSTANTIALLY THE FOLLOWING |
| FORM: ?TO THE BEST OF MY KNOWLEDGE AND BELIEF, THE |
| ABOVE DESCRIBED CONSTRUCTION OF ALL STRUCTURAL |
| LOAD-BEARING COMPONENTS COMPLIES WITH THE PERMITTED |
| DOCUMENTS AND THE SHORING AND RESHORING CONFORMS TO THE |
| SHORING AND RESHORING PLANS SUBMITTED TO THE |
| ENFORCEMENT AGENCY?. |