2016-09-06 06:12:46 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 NEC |
| COMMENTS: |
| |
| 1. 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC |
| MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS |
| OF FLORIDA STATUTES. |
| 2. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW INDETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| SECTION 107.3.5). |
| 3. PER FBC ENERGY CONSERVATION CODE, PROVIDE A NOTE TO |
| INDICATE THAT 75% OF LAMPS TO BE HIGH EFFICACY LAMPS, |
| AS THE EXTENT OF WORK IS SUBSTANTIAL. |
| 4. PROVIDE ALL INFORMATION AS SHOWN ON DRAWING |
| SUBMITTED ON A SET OF DRAWINGS PER ABOVE STATED CITY OF |
| WPB REQUIREMENTS, IN ORDER TO VERIFY SPACING |
| REQUIREMENTS OF RECEPTACLES AND LAYOUT. |
| |