Plan Review Notes For Permit 16090058 |
Permit Number |
16090058 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-09-08 18:46:31 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] FBC-E SECTION C405.2.4 EXTERIOR LIGHTING CONTROLS. | | LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION | | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION | | SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | PHOTOSENSOR. | | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | FOR A PERIOD OF AT LEAST 10 HOURS. ADD A NOTE TO THE | | PLANS. |
|