Plan Review Notes For Permit 16090054 |
Permit Number |
16090054 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-09-08 07:51:05 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, | | EXISTING BUILDING CODES | | PERMIT #16090054 | | 9/8/16 | | | | 1) THE NEW CLINIC OCCUPANCY SHALL BE IN COMPLIANCE WITH | | THE FBC-14 ENERGY CONSERVATION CODE PER SECTIONS C101.2 | | AND C101.4.4. SUBMIT DOCUMENTATION OF ENERGY | | COMPLIANCE- SEE SECTION C101.5.1. | | | | 2) CLARIFY HOW THE AIR DISTRIBUTION PLAN WAS DESIGNED- | | PROVIDE AC COOLING AND HEATING CALCULATIONS IN | | ACCORDANCE WITH SECTION C403.2.1, AND VENTILATION | | CALCULATIONS IN ACCORDANCE WITH TABLE 403.3 FBC-14 | | MECHANICAL. PROVIDE A SCHEDULE ON THE PLAN INDICATING | | THE REQUIRED AND PROVIDED CFM'S OF OUTDOOR AIR. | | | | 3) CLARIFY HOW O/A IS BEING PROVIDED TO THE SPACE, AND | | CONTROLLED- SEE SECTION C403.2.4.4 | | | | 4) REMOVE KEY NOTE #1 AT THE TRANSFER DUCT LOCATIONS | | AND REPLACE WITH KEY NOTE #3. | | | | 5) PROVIDE A LAB EQUIPMENT SCHEDULE AND SEE TABLE | | 403.3- AN EXHAUST SYSTEM MAY BE REQUIRED. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|