2016-09-08 07:51:051ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING CODES
 PERMIT #16090054
 9/8/16
  
 1) THE NEW CLINIC OCCUPANCY SHALL BE IN COMPLIANCE WITH
 THE FBC-14 ENERGY CONSERVATION CODE PER SECTIONS C101.2
 AND C101.4.4. SUBMIT DOCUMENTATION OF ENERGY
 COMPLIANCE- SEE SECTION C101.5.1.
  
 2) CLARIFY HOW THE AIR DISTRIBUTION PLAN WAS DESIGNED-
 PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH SECTION C403.2.1, AND VENTILATION
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.3 FBC-14
 MECHANICAL. PROVIDE A SCHEDULE ON THE PLAN INDICATING
 THE REQUIRED AND PROVIDED CFM'S OF OUTDOOR AIR.
  
 3) CLARIFY HOW O/A IS BEING PROVIDED TO THE SPACE, AND
 CONTROLLED- SEE SECTION C403.2.4.4
  
 4) REMOVE KEY NOTE #1 AT THE TRANSFER DUCT LOCATIONS
 AND REPLACE WITH KEY NOTE #3.
  
 5) PROVIDE A LAB EQUIPMENT SCHEDULE AND SEE TABLE
 403.3- AN EXHAUST SYSTEM MAY BE REQUIRED.
  