2016-09-07 14:06:59 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| 1) SHEET LS 00 - THERE ARE INCORRECT REFERENCES |
| INDICATED FOR THE FIRE CODE. |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| APPLICABLE CODES OR STANDARDS. |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2010 EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2010 EDITION. |
| CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 241, 2009 EDITION. |
| FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 10, 2010 EDITION. |
| ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| AIR CONDITION WORK SHALL COMPLY WITH NFPA 90 A & B, |
| 2012 EDITION |
| INSPECTION, TESTING & MAINTENANCE SHALL COMPLY WITH |
| NFPA 25, 2011 EDITION. |
| |
| PLEASE ENSURE COMPLIANCE WITH THE APPLICABLE CODES AND |
| IF REVISIONS ARE SUBMITTED PLEASE USE CLOUDED |
| NOTATIONS. |
| |
| |
| 2) SHEET LS 00 - THERE IS NO INDICATION FOR FIRE |
| SPRINKLER WORK. |
| |
| ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE |
| DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE |
| SAFETY CONTRACTORS. |
| ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| AND COMPLETE PROTECTION IS RETURNED. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| |