2016-09-06 05:59:241) SUBMIT TWO COPIES OF A PLAN THAT CLEARLY REFLECTS
 THE SCOPE OF WORK TO BE DONE. ONLY ONE COPY OF A PLAN
 HAS BEEN SUBMITTED AND THERE IS NO NOTE ON THE PLAN AS
 TO WHAT THE SCOPE OF WORK IS TO BE DONE.. WPB AMEND. TO
 FBC SEC. 107.1.
 2) INDICATE THE SIZE OF THE WATER SERVICES ON THE PLAN.
 3) INDICATE ON THE PLAN IF THERE IS AN EXISTING
 BACKFLOW PREVENTION DEVICE ON EACH WATER SERVICE. IF
 SO, INDICATE THE TYPE OF DEVICE. IF NOT, AN APPROVED
 LEAD FREE DEVICE MAY BE REQUIRED ON EACH WATER SERVICE
 PER THE CITY OF WPB CROSS-CONNECTION CONTROL MANUAL.
 PLEASE CONTACT STEPHEN HUNTER WWITH THE UTILITIES DEPT.
 AT 561-822-2242.
 4) SUBMIT TWO COPIES OF THE REQUIRED BACKFLOW
 PREVENTION DEVICES IF REQUIRED BY UTILITIES.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692