2016-09-06 06:26:28 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE CLARIFY MAIN BREAKER SIZE AS #3 CONDUCTOR IS | | UNDERSIZED FOR A 125AMP PANELBOARD. IF 100AMP MCB IS | | EXISTING SHOW ON PLANS. NEC 310.15B16 | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|