2016-09-01 16:09:01PERMIT #16081335
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLAN APPROVED PROVISO:
  
 1) ONLY 10 X10 SIZED TENTS SHALL BE ERECTED. TENTS
 SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM BUILDING
 STRUCTURES. TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL
 TYPE, OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT
 SIGNS ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE
 FEET. POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS. PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR
 THE CANOPY MATERIAL.
 2) FIRE EXTINGUISHERS (2A10BC) SHALL BE PROVIDED AND
 READILY ACCESSIBLE. TRAVEL DISTANCE TO EXTINGUISHERS
 SHALL NOT EXCEED 75 FEET.
 3) FIRE EXTINGUISHER (CLASS K) SHALL BE PROVIDED AT
 EVERY COOKING STATION.
 4) CUSTOMER STATED THAT ONLY CHARCOAL GRILLS WILL BE
 USED. ALL GRILLS SHALL BE A MINIMUM OF 10 FEET FROM ANY
 STRUCTURE.
 5) CUSTOMER STATED THAT A FENCE WAS BEING ERECTED. AT
 MINIMUM OF 2 EMERGENCY EXITS MUST BE PROVIDED. EXIT
 LOCATIONS SHALL BE OPPOSITE EACHOTHER AND SIGNS CLEARLY
 INDICATING THEIR LOCATIONS SHALL BE POSTED AND VISIBLE.
 6) GENERATORS (INCLUDING IF ANY USED FOR THE BOUNCE
 HOUSES) AND OTHER INTERNAL COMBUSTION POWER SOURCES
 SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET
 AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
  