2016-09-01 16:09:01 | PERMIT #16081335 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| PLAN APPROVED PROVISO: |
| |
| 1) ONLY 10 X10 SIZED TENTS SHALL BE ERECTED. TENTS |
| SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM BUILDING |
| STRUCTURES. TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL |
| TYPE, OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT |
| SIGNS ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE |
| FEET. POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS |
| LOCATIONS. PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR |
| THE CANOPY MATERIAL. |
| 2) FIRE EXTINGUISHERS (2A10BC) SHALL BE PROVIDED AND |
| READILY ACCESSIBLE. TRAVEL DISTANCE TO EXTINGUISHERS |
| SHALL NOT EXCEED 75 FEET. |
| 3) FIRE EXTINGUISHER (CLASS K) SHALL BE PROVIDED AT |
| EVERY COOKING STATION. |
| 4) CUSTOMER STATED THAT ONLY CHARCOAL GRILLS WILL BE |
| USED. ALL GRILLS SHALL BE A MINIMUM OF 10 FEET FROM ANY |
| STRUCTURE. |
| 5) CUSTOMER STATED THAT A FENCE WAS BEING ERECTED. AT |
| MINIMUM OF 2 EMERGENCY EXITS MUST BE PROVIDED. EXIT |
| LOCATIONS SHALL BE OPPOSITE EACHOTHER AND SIGNS CLEARLY |
| INDICATING THEIR LOCATIONS SHALL BE POSTED AND VISIBLE. |
| 6) GENERATORS (INCLUDING IF ANY USED FOR THE BOUNCE |
| HOUSES) AND OTHER INTERNAL COMBUSTION POWER SOURCES |
| SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET |
| AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR |
| ENCLOSURE. |
| |
| |