Plan Review Notes For Permit 16081327 |
Permit Number |
16081327 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-10-20 05:51:28 | 1) SUBMIT CALCULATIONS FOR COMBUSTION AIR. COMPLY WITH | | 2014 FBCR SEC.G2407.1, G2439.4, G2407.9.3. WHERE | | COMBUSTION AIR IS PROVIDED BY THE BUILDING?S MECHANICAL | | VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE | | SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE | | REQUIRED VENTILATION AIR. FGC SEC..304.9.3 OR FBCR | | G2407.9.3.2ND REQUEST. | | 2) LOCATION OF THE DRYER EXHAUST SHALL BE A MIN. OF 3 | | FEET FROM THE WINDOW PER 2014 FBCR SEC.M1502.3. | | 3) THE FUTURE GAS OUTLETS SHALL BE EQUIPPED WITH A | | SHUT-OFF VALE AND THE STEP DOWN REGULATOR INSTALLED | | WITH THE GAS OUT OF THE REGULATOR PLUGGED OR CAPPED.L | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|