Plan Review Notes
Plan Review Notes For Permit 16081327
Permit Number 16081327
Review Stop G
Sequence Number 1
Notes
Date Text
2016-09-02 04:57:481) THE PLANS ON RECORD SHOW A GAS DRYER BUT IT IS NOT
 SHOWNON THE GAS DRAWING. CLARIFY.
 2) SUBMIT A PLAN OF THE HOUSE SHOWING THE PROPOSED
 LOCARION OF THE FUTURE TANKLESS WATER HEATER IN
 RELATION TO OPERABLE WINDOWS AND DOORS IN THE
 STRUCTURE. THE TANKLESS WATER HEATER SHALL COMPLY WITH
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS IN REGARDS
 TO THE MINIMUM REQUIRED DISTANCES FROM OPERABLE DOORS,
 WINDOWS AND SOFFIT VENTS.
 3) SHOW THE CORRESPONDING EHD OF THE CSST. THERE ARE
 TWO DIFFERENT EHD'S WITH THE CSST AND EACH ONE CARRIES
 A DIFFERENT BTU LOAD. SEE 2014 FGC TABLE 402.4 (15).
 4) IF THE GAS DRYER IS ADDED TO THE SYSTEM THE PIPE
 SIZES SHALL BE RECHECKED AS THEY MAY BE UNDERSIZED WITH
 THE ADDED BTU LOAD.
 5) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
 6). SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 7) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
  
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  