2016-09-06 10:04:371ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16081314
 9/6/16
  
 1) PROVIDE A NARRATIVE FROM THE DESIGN PROFESSIONALS
 ITEMIZING ALL CHANGES MADE TO THE APPROVED DRAWINGS
 SINCE THE LAST APPROVED REVISION #16060333 SUBMITTED ON
 6/7/16. IT APPEARS THAT SOME OF THE RTU'S HAVE BEEN
 RELOCATED AND NEW GRID CEILINGS ARE NOW SHOWN IN THE
 SHOWROOM ARREA. PLEASE NOTE THAT ALL OF THE DUCTWORK
 AND DUCT SIZES MUST BE SHOWN ON THE PLANS INCLUDING THE
 MAIN TRUNKS WHICH ARE NOT SHOWN IN THIS NEW REVISION.
 ADDITIONALLY I AM SEEING THAT SOME OF THE FLEX DUCT
 SIZES ARE NOT SHOWN IN THE SALES WORKROOM AND IN THE
 ADJOINING ROOMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER