Plan Review Notes For Permit 16081314 |
Permit Number |
16081314 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-09-06 10:04:37 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16081314 | | 9/6/16 | | | | 1) PROVIDE A NARRATIVE FROM THE DESIGN PROFESSIONALS | | ITEMIZING ALL CHANGES MADE TO THE APPROVED DRAWINGS | | SINCE THE LAST APPROVED REVISION #16060333 SUBMITTED ON | | 6/7/16. IT APPEARS THAT SOME OF THE RTU'S HAVE BEEN | | RELOCATED AND NEW GRID CEILINGS ARE NOW SHOWN IN THE | | SHOWROOM ARREA. PLEASE NOTE THAT ALL OF THE DUCTWORK | | AND DUCT SIZES MUST BE SHOWN ON THE PLANS INCLUDING THE | | MAIN TRUNKS WHICH ARE NOT SHOWN IN THIS NEW REVISION. | | ADDITIONALLY I AM SEEING THAT SOME OF THE FLEX DUCT | | SIZES ARE NOT SHOWN IN THE SALES WORKROOM AND IN THE | | ADJOINING ROOMS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|