2016-09-12 08:59:29 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16081292/ PERMIT 16081296 TO BE |
| VOIDED! |
| ADD: 201 NARCISSUS ST. SUITE # 905/906 |
| CONT: PHILIP E. JOHNSON, INC. |
| TEL: 561-366-1034 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. SEPT. 12/ 2016 |
| ACTION: DENIED |
| |
| 1) PLEASE 2 PERMITS WERE SUBMITTED FOR THE COMBINING OF |
| SUITES 905 & 906. TO ACCOMPLISH THIS AN UNITY OF |
| PROPERTY IS REQUIRED. PERMIT 16081296 WILL BE VOIDED |
| AND THE FUNDS MOVED OVER TO PERMIT 16081292. |
| UNITY OF TITLE. |
| THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL |
| BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM |
| 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE |
| COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY |
| OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE |
| REQUIREMENTS MAY BE DEEMED NOT APPLICABLE. SEE WEBSITE |
| FOR APPLICATION: |
| HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| "APPLICATION FOR UNITY OF TITLE" |
| HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| -38-UNITYOFTITLE3.PDF |
| VINCENT J NOEL |
| SURVEYOR/REAL ESTATE SUPERVISOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33401 |
| PHONE: 494-1040 EXT: 1096 |
| FAX: 494-1116 |
| E-MAIL: [email protected] |
| ********************************************* |
| MANUEL JULIAN GONZALEZ |
| ENGINEERING PROJECT COORDINATOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET, 4TH FLOOR |
| WEST PALM BEACH, FL 33401 |
| (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| MAIN PHONE: (561) 822-1200 |
| DIRECT: (561) 494-1085 |
| FAX: (561) 494-1116 |
| MOBILE: (561) 644-7301 |
| EMAIL: [email protected] |
| |
| 2) THE FLOOR PLAN INDICATES THE USE OF ENGINEERED WOOD |
| FLOORING THROUGH OUT THE UNIT AND THE USE OF MARBLE, |
| TILE AND OR TRAVERTINE IN THE BATHROOMS. FOR BOTH TYPES |
| OF FLOOR FINISHES (3) REPORTS WILL BE REQUIRED FOR THE |
| ENGINEERED WOOD FLOORS AND 3 REPORTS FOR THE MARBLE, |
| TILE AND OR TRAVERTINE PRODUCTS. |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2014) |
| FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |