Plan Review Notes
Plan Review Notes For Permit 16081272
Permit Number 16081272
Review Stop B
Sequence Number 1
Notes
Date Text
2016-09-01 08:55:57BUILDING PLAN REVIEW
 W. P. B. REVISION: 16081272
 W. P. B. PERMIT: 15031312
 ADD: 333 FERN ST.
 CONT: KAST CONSTRUCTION
 CONTACT :
 TEL: (561)689-2910
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SEPT. 01/2016
 ACTION: DENIED
 KAST SUBMITTAL# SHOP 226
  
 1) THE SUBMITTAL FOR THE USE OF SHEETROCK BRAND
 ACOUSTICAL SEALANT LIST VARIOUS UL SYSTEMS FOR
 CONVENTIONAL WALL AND SHAFT WALL DESIGNS. THE 1ST
 CONVENTIONAL WALL DESGIN UL LISTING HW-D-0001 THE JOINT
 SYSTEM SHOWN AS 3A DOES NOT LIST THIS PRODUCT AS AN
 APPROVED JOINT FORMING MATERIAL.
  
 2010 FBC-B 714.3.1 THROUGH PENETRATIONS. THROUGH
 PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS SHALL
 COMPLY WITH SECTION 714.3.1.1 OR 714.3.1.2.
  
 EXCEPTION: WHERE THE PENETRATING ITEMS ARE STEEL,
 FERROUS OR COPPER PIPES, TUBES OR CONDUITS, THE ANNULAR
 SPACE BETWEEN THE PENETRATING ITEM AND THE
 FIRE-RESISTANCE-RATED WALL IS PERMITTED TO BE PROTECTED
 AS FOLLOWS:
  
 1. IN CONCRETE OR MASONRY WALLS WHERE THE PENETRATING
 ITEM IS A MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER AND
 THE AREA OF THE OPENING THROUGH THE WALL DOES NOT
 EXCEED 144 SQUARE INCHES (0.0929 M2), CONCRETE, GROUT
 OR MORTAR IS PERMITTED WHERE IT IS INSTALLED THE FULL
 THICKNESS OF THE WALL OR THE THICKNESS REQUIRED TO
 MAINTAIN THE FIRE-RESISTANCE RATING; OR
  
 2. THE MATERIAL USED TO FILL THE ANNULAR SPACE SHALL
 PREVENT THE PASSAGE OF FLAME AND HOT GASES SUFFICIENT
 TO IGNITE COTTON WASTE WHEN SUBJECTED TO ASTM E 119 OR
 UL 263 TIME-TEMPERATURE FIRE CONDITIONS UNDER A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AT THE LOCATION OF THE PENETRATION FOR THE
 TIME PERIOD EQUIVALENT TO THE FIRE-RESISTANCE RATING OF
 THE CONSTRUCTION PENETRATED.
  
 714.3.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN
 APPROVED FIRERESISTANCE-RATED ASSEMBLY.
  
 714.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH
 PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN
 ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN
 THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL
 PENETRATED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  