2016-09-01 08:55:57 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 16081272 |
| W. P. B. PERMIT: 15031312 |
| ADD: 333 FERN ST. |
| CONT: KAST CONSTRUCTION |
| CONTACT : |
| TEL: (561)689-2910 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS |
| ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: SEPT. 01/2016 |
| ACTION: DENIED |
| KAST SUBMITTAL# SHOP 226 |
| |
| 1) THE SUBMITTAL FOR THE USE OF SHEETROCK BRAND |
| ACOUSTICAL SEALANT LIST VARIOUS UL SYSTEMS FOR |
| CONVENTIONAL WALL AND SHAFT WALL DESIGNS. THE 1ST |
| CONVENTIONAL WALL DESGIN UL LISTING HW-D-0001 THE JOINT |
| SYSTEM SHOWN AS 3A DOES NOT LIST THIS PRODUCT AS AN |
| APPROVED JOINT FORMING MATERIAL. |
| |
| 2010 FBC-B 714.3.1 THROUGH PENETRATIONS. THROUGH |
| PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS SHALL |
| COMPLY WITH SECTION 714.3.1.1 OR 714.3.1.2. |
| |
| EXCEPTION: WHERE THE PENETRATING ITEMS ARE STEEL, |
| FERROUS OR COPPER PIPES, TUBES OR CONDUITS, THE ANNULAR |
| SPACE BETWEEN THE PENETRATING ITEM AND THE |
| FIRE-RESISTANCE-RATED WALL IS PERMITTED TO BE PROTECTED |
| AS FOLLOWS: |
| |
| 1. IN CONCRETE OR MASONRY WALLS WHERE THE PENETRATING |
| ITEM IS A MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER AND |
| THE AREA OF THE OPENING THROUGH THE WALL DOES NOT |
| EXCEED 144 SQUARE INCHES (0.0929 M2), CONCRETE, GROUT |
| OR MORTAR IS PERMITTED WHERE IT IS INSTALLED THE FULL |
| THICKNESS OF THE WALL OR THE THICKNESS REQUIRED TO |
| MAINTAIN THE FIRE-RESISTANCE RATING; OR |
| |
| 2. THE MATERIAL USED TO FILL THE ANNULAR SPACE SHALL |
| PREVENT THE PASSAGE OF FLAME AND HOT GASES SUFFICIENT |
| TO IGNITE COTTON WASTE WHEN SUBJECTED TO ASTM E 119 OR |
| UL 263 TIME-TEMPERATURE FIRE CONDITIONS UNDER A MINIMUM |
| POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) |
| OF WATER AT THE LOCATION OF THE PENETRATION FOR THE |
| TIME PERIOD EQUIVALENT TO THE FIRE-RESISTANCE RATING OF |
| THE CONSTRUCTION PENETRATED. |
| |
| 714.3.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES. |
| PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN |
| APPROVED FIRERESISTANCE-RATED ASSEMBLY. |
| |
| 714.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH |
| PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN |
| ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM |
| POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) |
| OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN |
| THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL |
| PENETRATED. |
| |