Plan Review Notes
Plan Review Notes For Permit 16081262
Permit Number 16081262
Review Stop P
Sequence Number 1
Notes
Date Text
2016-09-28 10:22:221ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. IF THIS PERMIT IS ONLY FOR GARAGE PLEASE REMOVE ANY
 DETAILS AND RISER DIAGRAMS FROM PLAN SET THAT DO NOT
 REFLECT THE SCOPE OF WORK FOR THIS PROJECT. WPB AMEND
 TO FBC 107.2.1
  
 2. THE KITCHEN SINK DRAIN ON THE SECOND FLOOR SHALL
 CONNECT TO BUILDING DRAIN DOWN STREAM OF BATHROOM GROUP
 IT CAN NOT CONNECT BETWEEN BATHROOM FIXTURES. PER FBC
 PL 912.1
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.