Plan Review Notes For Permit 16081262 |
Permit Number |
16081262 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-09-07 18:20:03 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] CORRECT DEFFICIENCY IN PANEL SCHEDULE "LA" FOR THE | | DRYER BREAKER FROM 40 AMPS TO 30 AMPS TYPICAL. | | | | 2] GARAGE DOOR OPENER RECEPTACLE SHALL BE GFCI | | PROTECTED PER NEC 210.8(A)(2) | | | | 3] ADD A NOTE FOR TAMPER-RESISTANT RECEPTACLES IN | | ACCORDANCE WITH NEC 406.12 |
|