Plan Review Notes
Plan Review Notes For Permit 16081262
Permit Number 16081262
Review Stop B
Sequence Number 1
Notes
Date Text
2016-09-22 17:28:12RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- DESIGN PRESSURES FOR G2 DOOR DON'T CORRESPOND TO
 EXPOSURE "D". REVISE DESIGN PRESSURES SHOWN ON SHEET
 A-3 AND A-3.10. SEC. R301.1 FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 3- DESIGN CRITERIA ON SHEET SP-1.0 REFERENCES ASCE
 7-14. THE ASCE REFERENCED IN THE FBC 2014 IS THE ASCE
 7-10 NOT 14. REVISE AS REQUIRED. CHAPTER 553 F.S.
  
 4- GARAGE IS NOT ALLOWED TO BE CONNECTED TO A ROOM THAT
 IS USED FOR SLEEPING. ACCORDING TO PLANS SUBMITTED THE
 GARAGE IS LEADING DIRECTLY TO AN SLEEPING AREA ON THE
 SECOND FLOOR. REVISE AS REQUIRED TO COMPLY WITH THIS
 REQUIREMENT.. ALSO, PROVIDE COMPLIANCE WITH THE
 DWELLING/GARAGE OPENING PROTECTION AS REQUIRED BY SEC.
 R302.5.1 FBC-RESIDENTIAL. PROVIDE COMPLETE
 SPECIFICATIONS FOR THE TYPE OF DOOR AND INCLUDE THE
 SELF CLOSING DEVICE.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF FABRIC AWNINGS SHOWN
 ON THE PROPOSED SOUTH ELEVATION. SEC. R301.1
 FBC-RESIDENTIAL.
  
 6- PROVIDE DETAILS/SPECIFICATIONS FOR THE ROOF SLOPE TO
 SHOW COMPLIANCE WITH THE 1/4 PER FOOT SLOPE REQUIRED BY
 SEC. R905.11.1 FBC-RESIDENTIAL. REVISE SPECIFICATIONS
 FOR THE ROOF TRUSSES SHOWN ON WALL SECTION ON SHEET
 A-3.21 AND CLEARLY PROVIDE THE SPECIFICATIONS ON THE
 STRUCTURAL DRAWINGS.
  
 7- PROVIDE ICYNENE FOAM INSULATION ICC EVALUATION
 REPORT (2 COPIES) SHOWING COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL. DESIGNER OF RECORD TO REVIEW/APPROVE
 PRIOR TO SUBMITTAL.
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF STAIRWAY SHOWING
 COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5 AND THE
 REQUIREMENTS OF SEC. R311.7 FBC-RESIDENTIAL.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY
 SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
  
 B) OPAQUE FIBERGLASS DOOR AS SPECIFIED ON PLANS. NOTE:
 PROVIDE CURRENT PRODUCT APPROVAL DRAWINGS DRAWING
 FL-17184-11 SUBMITTED IS FOR THE 2010 FBC. SEE GENERAL
 NOTE #1 ON PAGE 1 OF 7. NEED TO PROVIDE PRODUCT
 APPROVAL FOR THE CURRENT 2014 FBC. NOTE: VERIFY THAT
 PRODUCT APPROVAL MEETS THE G2 DOOR REVISED DESIGN
 PRESSURES.
  
 C) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED
 ON THE TRUSS ANCHOR SCHEDULE AND ALL OTHER DETAILS.
 UPDATE THE FLORIDA PRODUCT APPROVAL NUMBER LISTED ON
 THE TRUSS ANCHOR SCHEDULE. NEED THE 2014 CODE VERSION
 NOT THE 2010 CODE VERSION. AND, LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH CONNECTOR
 SPECIFIED ON THE DETAILS PROVIDED.
  
 10- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 11- FLAT ROOF MODIFIED BITUMEN NOA 14-0529.02
 SUBMITTED: CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED. ONLY ASSEMBLIES WITH
 GENERAL LIMITATION #7 WILL ALLOW RAS 117 CALCULATIONS.
 ASSEMBLIES WITH GENERAL LIMITATION #9 DON'T ALLOW RAS
 117 CALCULATIONS. SEE LAST PAGE OF NOA SUBMITTED.
  
 12- TRUSS PACKAGE SUBMITTED:
 A) COVER PAGE NEEDS THE INFORMATION OF THE STRUCTURAL
 ENGINEER OF RECORD AS REQUIRED BY 61G15-31.003 FAC.
  
 B) THE INDIVIDUAL TRUSS DRAWINGS NEED THE TITLE BLOCK
 OF THE TRUSS ENGINEER AS REQUIRED BY 61G15-31.003 FAC.
  
 C) TRUSS PACKAGE NEEDS TO BE APPROVED BY THE ENGINEER
 OF RECORD AS REQUIRED BY 61G15-30.005 FAC.
  
 NOTE: THERE ARE TWO ADDITIONAL COPIES OF STRUCTURAL
 DRAWINGS S01 AND S02 DWGS ON ONE SET. PLEASE REMOVE ONE
 COPY.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS TO RESUBMITTED SETS.
 SUBMIT OLD DRAWINGS FOR REFERENCE.
  