2016-09-22 17:28:12 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| CODE. |
| |
| 2- DESIGN PRESSURES FOR G2 DOOR DON'T CORRESPOND TO |
| EXPOSURE "D". REVISE DESIGN PRESSURES SHOWN ON SHEET |
| A-3 AND A-3.10. SEC. R301.1 FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| |
| 3- DESIGN CRITERIA ON SHEET SP-1.0 REFERENCES ASCE |
| 7-14. THE ASCE REFERENCED IN THE FBC 2014 IS THE ASCE |
| 7-10 NOT 14. REVISE AS REQUIRED. CHAPTER 553 F.S. |
| |
| 4- GARAGE IS NOT ALLOWED TO BE CONNECTED TO A ROOM THAT |
| IS USED FOR SLEEPING. ACCORDING TO PLANS SUBMITTED THE |
| GARAGE IS LEADING DIRECTLY TO AN SLEEPING AREA ON THE |
| SECOND FLOOR. REVISE AS REQUIRED TO COMPLY WITH THIS |
| REQUIREMENT.. ALSO, PROVIDE COMPLIANCE WITH THE |
| DWELLING/GARAGE OPENING PROTECTION AS REQUIRED BY SEC. |
| R302.5.1 FBC-RESIDENTIAL. PROVIDE COMPLETE |
| SPECIFICATIONS FOR THE TYPE OF DOOR AND INCLUDE THE |
| SELF CLOSING DEVICE. |
| |
| 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| CONSTRUCTION AND INSTALLATION OF FABRIC AWNINGS SHOWN |
| ON THE PROPOSED SOUTH ELEVATION. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| 6- PROVIDE DETAILS/SPECIFICATIONS FOR THE ROOF SLOPE TO |
| SHOW COMPLIANCE WITH THE 1/4 PER FOOT SLOPE REQUIRED BY |
| SEC. R905.11.1 FBC-RESIDENTIAL. REVISE SPECIFICATIONS |
| FOR THE ROOF TRUSSES SHOWN ON WALL SECTION ON SHEET |
| A-3.21 AND CLEARLY PROVIDE THE SPECIFICATIONS ON THE |
| STRUCTURAL DRAWINGS. |
| |
| 7- PROVIDE ICYNENE FOAM INSULATION ICC EVALUATION |
| REPORT (2 COPIES) SHOWING COMPLIANCE WITH SEC. R316 |
| FBC-RESIDENTIAL. DESIGNER OF RECORD TO REVIEW/APPROVE |
| PRIOR TO SUBMITTAL. |
| |
| 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| CONSTRUCTION AND INSTALLATION OF STAIRWAY SHOWING |
| COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5 AND THE |
| REQUIREMENTS OF SEC. R311.7 FBC-RESIDENTIAL. |
| |
| 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY |
| SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE |
| CALCULATED DESIGN PRESSURES. |
| |
| B) OPAQUE FIBERGLASS DOOR AS SPECIFIED ON PLANS. NOTE: |
| PROVIDE CURRENT PRODUCT APPROVAL DRAWINGS DRAWING |
| FL-17184-11 SUBMITTED IS FOR THE 2010 FBC. SEE GENERAL |
| NOTE #1 ON PAGE 1 OF 7. NEED TO PROVIDE PRODUCT |
| APPROVAL FOR THE CURRENT 2014 FBC. NOTE: VERIFY THAT |
| PRODUCT APPROVAL MEETS THE G2 DOOR REVISED DESIGN |
| PRESSURES. |
| |
| C) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED |
| ON THE TRUSS ANCHOR SCHEDULE AND ALL OTHER DETAILS. |
| UPDATE THE FLORIDA PRODUCT APPROVAL NUMBER LISTED ON |
| THE TRUSS ANCHOR SCHEDULE. NEED THE 2014 CODE VERSION |
| NOT THE 2010 CODE VERSION. AND, LIST THE FLORIDA |
| PRODUCT APPROVAL NUMBER NEXT TO EACH CONNECTOR |
| SPECIFIED ON THE DETAILS PROVIDED. |
| |
| 10- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS |
| AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 11- FLAT ROOF MODIFIED BITUMEN NOA 14-0529.02 |
| SUBMITTED: CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS |
| GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE: |
| IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES |
| FOR ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117 |
| CALCULATIONS WILL BE REQUIRED. ONLY ASSEMBLIES WITH |
| GENERAL LIMITATION #7 WILL ALLOW RAS 117 CALCULATIONS. |
| ASSEMBLIES WITH GENERAL LIMITATION #9 DON'T ALLOW RAS |
| 117 CALCULATIONS. SEE LAST PAGE OF NOA SUBMITTED. |
| |
| 12- TRUSS PACKAGE SUBMITTED: |
| A) COVER PAGE NEEDS THE INFORMATION OF THE STRUCTURAL |
| ENGINEER OF RECORD AS REQUIRED BY 61G15-31.003 FAC. |
| |
| B) THE INDIVIDUAL TRUSS DRAWINGS NEED THE TITLE BLOCK |
| OF THE TRUSS ENGINEER AS REQUIRED BY 61G15-31.003 FAC. |
| |
| C) TRUSS PACKAGE NEEDS TO BE APPROVED BY THE ENGINEER |
| OF RECORD AS REQUIRED BY 61G15-30.005 FAC. |
| |
| NOTE: THERE ARE TWO ADDITIONAL COPIES OF STRUCTURAL |
| DRAWINGS S01 AND S02 DWGS ON ONE SET. PLEASE REMOVE ONE |
| COPY. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS TO RESUBMITTED SETS. |
| SUBMIT OLD DRAWINGS FOR REFERENCE. |
| |