Plan Review Notes
Plan Review Notes For Permit 16081241
Permit Number 16081241
Review Stop B
Sequence Number 1
Notes
Date Text
2016-09-06 10:16:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. WIND DESIGN CRITERIA IS NOT CLEAR. SEE FBC 1603.1.4.
 GENERAL NOTE 2 DOES NOT STATE WHETHER THIS WAS DESIGNED
 TO VULT OR VASD.
  
 2. PLEASE EXPLAIN THE RATIONALE OF DESIGNING TO RISK
 CATEGORY 1, FBC TABLE 1604.5, OR REVISE TO A MINIMUM
 RISK CATEGORY II.
  
 3. DELEGATED ENGINEERING AND SHOP DRAWINGS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL, FBC
 107. THE ARCHITECT'S PLAN (A0) EXCLUDES THE FENCE FROM
 THIS PERMIT. PLEASE REVISE PLAN AND HAVE ENGINEERING
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 4. GENERAL NOTE 7 REFERS TO THE SECTION FOR RESIDENTIAL
 SWIMMING POOLS (FBC 454.2.17). SEE DEFINITIONS; A POOL
 ASSOCIATED WITH FIVE OR MORE RESIDENTIAL UNITS IS
 CONSIDERED A PUBLIC SWIMMING POOL, FBC 454.1. THE POOL
 FENCE IS TO COMPLY WITH FBC 454.1.3.1.9.
  
 5. FBC TABLE 1004.1.2, POOL DECK AREA SHOULD UTILIZE 15
 SF PER PERSON FOR THE POOL DECK RATHER THAN 50 SF PER
 PERSON, PLEASE REVISE OCCUPANT LOAD CALCULATIONS.
  
 6. REVISE PLAN TO INCLUDE THE OCCUPANCY CLASSIFICATION
 FOR THE POOL AND PLAYGROUND AREAS (A5), FBC 303.6.
  
 7. FBC 1008.2, GATES IN THE MEANS OF EGRESS ARE TO
 CONFORM TO THE REQUIREMENTS FOR DOORS. FBC 1008.1.10,
 PANIC DEVICES ARE REQUIRED IN ASSEMBLY OCCUPANCY WITH
 AN OCCUPANT LOAD OF 50 OR MORE.
  
 8. AS TWO MEANS OF EGRESS ARE REQUIRED FROM BOTH AREAS,
 IT APPEARS THAT BOTH THE POOL AREA AND THE PLAYGROUND
 AREA UTILIZE THE POOL CABANA AS A MEANS OF EGRESS. ONLY
 ONE DOOR IS SHOWN; IS THE OTHER SIDE OPEN? OR IS THE
 FRONT DOOR A GATE? EITHER REVISE PLAN TO PROVIDE A
 SECOND MEANS OF EGRESS FOR EACH AREA OR REVISE PLAN TO
 SHOW HOW THE POOL CABANA COMPLIES AS A MEANS OF EGRESS
 (PANIC DEVICES ON THE EXIT, INCLUDE DOOR WIDTHS). SEE
 ALSO FBC 1027.1 WHICH STATES "THE EXIT DISCHARGE SHALL
 NOT REENTER A BUILDING." IF THE CABANA IS TO BE A PART
 OF THE EXIT STRATEGY, PLEASE SEND AN EMAIL PRIOR TO
 RESUBMITTAL TO CONFIRM THAT THIS WILL BE PERMITTED IN
 THIS CASE.
  
 9. REVISE PLAN TO INCLUDE WIDTH OF ALL GATES IN THE
 MEANS OF EGRESS, FBC 107, FBC 10.
  
 10. REVISE PLAN TO SHOW ACCESSIBLE ROUTE TO THE PUBLIC
 WAY; SEE FBC 1007.1, FBC 5TH EDITION ACCESSIBILITY 207,
 IBC 2000 1003.2.13, IBC 2003 1007.2.
  
 11. FBC 107, THE APPLICATION IS FOR SIX GATES AND
 FENCING. PLEASE NOTE THE GATES; THE SAME GRAPHIC WAS
 USED FOR BOTH GATES AND DOORS ON THE PLAN. LOCATION OF
 THE SIX GATES IS NOT CLEAR.
  
  