2016-09-13 09:16:25 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: |
| JOB ADDRESS: 2324 EMBASSY DR. |
| DESCRIPTION: BATHROOM RENOVATION |
| MASTER PERMIT: 16081177 |
| |
| BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| SUBMITTED CORRECTIONS. |
| |
| 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS TO THE |
| FBC-B REQUIRES THAT THE CONSTRUCTION DOCUMENTS BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE PROPOSED WORK AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR |
| SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL |
| INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE, |
| THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND |
| SIGNATURE SHALL APPEAR ON ALL DOCUMENTS). THE DRAWINGS |
| SHALL BE SIGNED, INCLUDE THE SCOPE OF WORK AND THE |
| APPLICABLE DESIGN CODE EDITION. |
| 2. YOU SHALL SECURE AND ELECTRICAL SUB PERMIT WITH |
| ACCOMPANYING ELECTRICAL DRAWINGS. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |