2016-12-21 09:50:36 | 3RD REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | PASSED WITH THE FOLLOWING PROVISO'S | | | | 1] IN ALL CHILD CARE FACILITIES, ALL NONLOCKING-TYPE, | | 125-VOLT, 15- AND 20- AMPERE RECEPTACLES SHALL BE | | LISTED TAMPER-RESISTANT RECEPTACLES. NEC 406.14 | | | | 2] FBC-B 1006.2. EMERGENCY LIGHTING IS REQUIRED | | | | 3] FBC-B 1011. EXIT SIGNAGE REQUIRED. | | |
|