Plan Review Notes For Permit 16081168 |
Permit Number |
16081168 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-11-22 16:14:04 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16081168 | | 11/22/16 | | | | 1) 2ND REQUEST FOR A VENTILATION CALCULATION FOR THE | | NEW DAY CARE. REFER TO TABLE 403.3: DAY CARE O/A RATE | | IS CALCULATED AT 10 CFM PER OCCUPANT PLUS 0.18/SF. | | TOTAL- 294 CFMS OF O/A IS REQUIRED FOR THE NEW | | OCCUPANCY. A) SHOW THE EXISTING DUCT DROPS AND | | DIFFUSERS IN THE DAY CARE ROOM AND INCLUDE DUCT AND | | DIFFUSER SIZES AND SUPPLY CFMS AT EACH DROP. B) | | INDICATE THE COOLING AND HEATING CAPACITIES OF THE | | EXISTING SYSTEM AND THE TOTAL SUPPLY CFMS THE SYSTEM | | CAN PRODUCE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|