Date |
Text |
2016-09-23 14:53:46 | 1ST REVIEW |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| PLUMBING COMMENTS |
| |
| 1) THE LIFE SAFETY SHEET INDICATES THIS IS A CHANGE OF |
| OCCUPANCY DAYCARE WITH AN OCCUPANT LOAD OF 31 OCCUPANTS |
| (20 NET). PLEASE PROVIDE THE SQUARE FOOTAGE OF THE |
| CHANGE OF OCCUPANCY AND SEE FBC-B TABLE 10041.2 THE |
| OCCUPANT LOAD FACTOR IS (35 NET). |
| |
| 2) THE CODE ANALYSIS INDICATES THE OCCUPANCY AS AN (D) |
| DAYCARE OCCUPANCY. PLEASE INDICATE AS TO WHICH TYPE OF |
| DAYCARE/ EDUCATIONAL FACILITY THIS USE WILL FALL INTO: |
| 2014 FBC-B 305.2 GROUP E, DAY CARE FACILITIES. THIS |
| GROUP INCLUDES BUILDINGS AND STRUCTURES OR PORTIONS |
| THEREOF OCCUPIED BY MORE THAN FIVE CHILDREN OLDER THAN |
| 2 1/2 YEARS OF AGE WHO RECEIVE EDUCATIONAL, SUPERVISION |
| OR PERSONAL CARE SERVICES FOR FEWER THAN 24 HOURS PER |
| DAY. |
| OR |
| 308.6.1 CLASSIFICATION AS GROUP E. A CHILD DAY CARE |
| FACILITY THAT PROVIDES CARE FOR MORE THAN FIVE BUT NO |
| MORE THAN 100 CHILDREN 2 1/2 YEARS OR LESS OF AGE, |
| WHERE THE ROOMS IN WHICH THE CHILDREN ARE CARED FOR ARE |
| LOCATED ON A LEVEL OF EXIT DISCHARGE SERVING SUCH ROOMS |
| AND EACH OF THESE CHILD CARE ROOMS HAS AN EXIT DOOR |
| DIRECTLY TO THE EXTERIOR, SHALL BE CLASSIFIED AS GROUP |
| E. |
| OR |
| CHILDREN 2 1/2 YEARS OF AGE OR LESS USUALLY ARE NOT |
| ABLE TO RECOGNIZE AN EMERGENCY SITUATION, MAY NOT |
| RESPOND APPROPRIATELY OR MAY NOT BE ABLE TO EGRESS |
| WITHOUT ASSISTANCE; THUS FACILITIES THAT HAVE MORE THAN |
| 5 CHILDREN 2 1/2 YEARS OF AGE OR LESS ARE CLASSIFIED AS |
| CHILD CARE FACILITIES AND CONSIDERED TO BE GROUP I-4. |
| |
| 3) THE PLAN INDICATES A PROPOSED DAYCARE CLASSROOM, IS |
| THIS ROOM BEING ADDED TO AN EXISTING DAYCARE? THE PLANS |
| DO NOT SHOW WHERE THE TOILET FACILITIES FOR THE |
| DAYCARE, NOR THE FACILITIES TO BE USED FOR THE ADULTS? |
| |
| |
| 4A) 468.3.5.2 TEACHER TOILETS. FACULTY AND STAFF |
| TOILETS SHALL BE SEPARATE FROM STUDENT TOILETS. |
| |
| 4B) 468.3.5.5 WALLS. WALLS IN TOILET ROOMS SHALL BE |
| IMPERVIOUS TO A HEIGHT OF AT LEAST 4 FEET (1219 MM) |
| ABOVE THE FLOOR. WALLS IN KITCHENS, SCULLERIES, CAN |
| WASH AREAS, AND SHOWER ROOMS SHALL BE IMPERVIOUS TO A |
| HEIGHT OF AT LEAST 6 FEET (1829 MM) ABOVE THE FLOOR. |
| TOILET AND SHOWER PARTITIONS SHALL BE IMPERVIOUS. |
| |
| 4C) 2014 FBC-ACCESS. CODE 604.1 GENERAL. WATER CLOSETS |
| AND TOILET COMPARTMENTS SHALL COMPLY WITH 604.2 THROUGH |
| 604.8. EXCEPTION: WATER CLOSETS AND TOILET COMPARTMENTS |
| FOR CHILDREN?S USE SHALL BE PERMITTED TO COMPLY WITH |
| 604.9. 604.9 WATER CLOSETS AND TOILET COMPARTMENTS FOR |
| CHILDREN?S USE. |
| |
| 4D) WATER CLOSETS AND TOILET COMPARTMENTS FOR |
| CHILDREN?S USE SHALL COMPLY WITH 604.9. |
| |
| 4E) 468.3.4 DIAPER CHANGING STATIONS. A DIAPER CHANGING |
| STATION SHALL BE LOCATED IN OR ADJACENT TO ANY |
| CLASSROOM WHERE CHILDREN WEARING DIAPERS ARE IN |
| ATTENDANCE. A HAND WASHING LAVATORY SHALL BE PROVIDED |
| WITHIN THE CHANGING STATION AREA. ACCESS SHALL BE |
| PROVIDED TO THE LAVATORY WITHOUT OPENING DOORS OR |
| TOUCHING A HANDLE. |
| |
| 5) PLEASE INDICATE PREVIOUS OCCUPANCY USE. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 6) PROVIDE A FLOOR PLAN CLEARLY SHOWING ALL PLUMBING |
| FIXTURES . PER WPB AMEND TO FBC 107.2.1 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |