Plan Review Notes
Plan Review Notes For Permit 16081168
Permit Number 16081168
Review Stop P
Sequence Number 1
Notes
Date Text
2016-09-23 14:53:461ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS
  
 1) THE LIFE SAFETY SHEET INDICATES THIS IS A CHANGE OF
 OCCUPANCY DAYCARE WITH AN OCCUPANT LOAD OF 31 OCCUPANTS
 (20 NET). PLEASE PROVIDE THE SQUARE FOOTAGE OF THE
 CHANGE OF OCCUPANCY AND SEE FBC-B TABLE 10041.2 THE
 OCCUPANT LOAD FACTOR IS (35 NET).
  
 2) THE CODE ANALYSIS INDICATES THE OCCUPANCY AS AN (D)
 DAYCARE OCCUPANCY. PLEASE INDICATE AS TO WHICH TYPE OF
 DAYCARE/ EDUCATIONAL FACILITY THIS USE WILL FALL INTO:
 2014 FBC-B 305.2 GROUP E, DAY CARE FACILITIES. THIS
 GROUP INCLUDES BUILDINGS AND STRUCTURES OR PORTIONS
 THEREOF OCCUPIED BY MORE THAN FIVE CHILDREN OLDER THAN
 2 1/2 YEARS OF AGE WHO RECEIVE EDUCATIONAL, SUPERVISION
 OR PERSONAL CARE SERVICES FOR FEWER THAN 24 HOURS PER
 DAY.
 OR
 308.6.1 CLASSIFICATION AS GROUP E. A CHILD DAY CARE
 FACILITY THAT PROVIDES CARE FOR MORE THAN FIVE BUT NO
 MORE THAN 100 CHILDREN 2 1/2 YEARS OR LESS OF AGE,
 WHERE THE ROOMS IN WHICH THE CHILDREN ARE CARED FOR ARE
 LOCATED ON A LEVEL OF EXIT DISCHARGE SERVING SUCH ROOMS
 AND EACH OF THESE CHILD CARE ROOMS HAS AN EXIT DOOR
 DIRECTLY TO THE EXTERIOR, SHALL BE CLASSIFIED AS GROUP
 E.
 OR
 CHILDREN 2 1/2 YEARS OF AGE OR LESS USUALLY ARE NOT
 ABLE TO RECOGNIZE AN EMERGENCY SITUATION, MAY NOT
 RESPOND APPROPRIATELY OR MAY NOT BE ABLE TO EGRESS
 WITHOUT ASSISTANCE; THUS FACILITIES THAT HAVE MORE THAN
 5 CHILDREN 2 1/2 YEARS OF AGE OR LESS ARE CLASSIFIED AS
 CHILD CARE FACILITIES AND CONSIDERED TO BE GROUP I-4.
  
 3) THE PLAN INDICATES A PROPOSED DAYCARE CLASSROOM, IS
 THIS ROOM BEING ADDED TO AN EXISTING DAYCARE? THE PLANS
 DO NOT SHOW WHERE THE TOILET FACILITIES FOR THE
 DAYCARE, NOR THE FACILITIES TO BE USED FOR THE ADULTS?
  
  
 4A) 468.3.5.2 TEACHER TOILETS. FACULTY AND STAFF
 TOILETS SHALL BE SEPARATE FROM STUDENT TOILETS.
  
 4B) 468.3.5.5 WALLS. WALLS IN TOILET ROOMS SHALL BE
 IMPERVIOUS TO A HEIGHT OF AT LEAST 4 FEET (1219 MM)
 ABOVE THE FLOOR. WALLS IN KITCHENS, SCULLERIES, CAN
 WASH AREAS, AND SHOWER ROOMS SHALL BE IMPERVIOUS TO A
 HEIGHT OF AT LEAST 6 FEET (1829 MM) ABOVE THE FLOOR.
 TOILET AND SHOWER PARTITIONS SHALL BE IMPERVIOUS.
  
 4C) 2014 FBC-ACCESS. CODE 604.1 GENERAL. WATER CLOSETS
 AND TOILET COMPARTMENTS SHALL COMPLY WITH 604.2 THROUGH
 604.8. EXCEPTION: WATER CLOSETS AND TOILET COMPARTMENTS
 FOR CHILDREN?S USE SHALL BE PERMITTED TO COMPLY WITH
 604.9. 604.9 WATER CLOSETS AND TOILET COMPARTMENTS FOR
 CHILDREN?S USE.
  
 4D) WATER CLOSETS AND TOILET COMPARTMENTS FOR
 CHILDREN?S USE SHALL COMPLY WITH 604.9.
  
 4E) 468.3.4 DIAPER CHANGING STATIONS. A DIAPER CHANGING
 STATION SHALL BE LOCATED IN OR ADJACENT TO ANY
 CLASSROOM WHERE CHILDREN WEARING DIAPERS ARE IN
 ATTENDANCE. A HAND WASHING LAVATORY SHALL BE PROVIDED
 WITHIN THE CHANGING STATION AREA. ACCESS SHALL BE
 PROVIDED TO THE LAVATORY WITHOUT OPENING DOORS OR
 TOUCHING A HANDLE.
  
 5) PLEASE INDICATE PREVIOUS OCCUPANCY USE. PER WPB
 AMEND TO FBC 107.2.1
  
 6) PROVIDE A FLOOR PLAN CLEARLY SHOWING ALL PLUMBING
 FIXTURES . PER WPB AMEND TO FBC 107.2.1
  
  
  
  
  
  
  
  
  
  
  