2016-09-08 16:35:471ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16081168
 9/8/16
  
 1) PLEASE REVIEW SECTION C101.4.4 FBC-14 ENERGY
 CONSERVATION AS IT APPLIES TO THE PROPOSED CHANGE OF
 OCCUPANCY AND SHOW COMPLIANCE.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE A MINIMUM VENTILATION CALCULATION FOR THE
 NEW DAYCARE CLASSROOM. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 3) SUBMIT MECHANICAL PLANS SHOWING ALL PROPOSED
 ALTERATIONS TO THE EXISTING HVAC SYSTEMS.
  
 4) ADVISORY: THE SUBMITTED PLANS ARE INCOMPLETE. PLEASE
 REVIEW THE BUILDING REVIEW COMMENTS- ADDITIONAL
 MECHANICAL COMMENTS MAY FOLLOW RESUBMITTAL OF CORRECTED
 PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER