Plan Review Notes For Permit 16081096 |
Permit Number |
16081096 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-09-26 10:25:40 | 1ST REVIEW | | | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | 1. THE PLUMBING CODE REQUIRES SEPARATE FACILITIES FOR | | MEN AND WOMEN , IT WILL BE NECESSARY TO INDICATE ON THE | | PLAN WHICH BATHROOMS WILL BE FOR MEN AND WHICH | | BATHROOMS WILL BE FOR WOMEN. | | PER. FBC PL 403.2 SEPARATE FACILITIES. | | WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE | | FACILITIES SHALL BE PROVIDED FOR EACH SEX. | | 403.4 SIGNAGE. | | REQUIRED PUBLIC FACILITIES SHALL BE DESIGNATED BY A | | LEGIBLE SIGN FOR EACH SEX. SIGNS SHALL BE READILY | | VISIBLE AND LOCATED NEAR THE ENTRANCE TO EACH TOILET | | FACILITY. SIGNS FOR ACCESSIBLE TOILET FACILITIES SHALL | | COMPLY WITH THE FLORIDA BUILDING CODE, ACCESSIBILITY | | | | 2. PLEASE INDICATE ON THE PLAN WHAT THE OPEN ROOM #108 | | WILL BE USED FOR ALSO GIVE OCCUPANT LOAD. PER WPB AMEND | | TO FBC 107.2.1 | | | | 3. IF THE OPEN ROOM #108 IS AN ASSEMBLY OCCUPANCY YOU | | WILL BE REQUIRED TO COMPLY WITH. FBC PL 403.1.3 POTTY | | PARITY. | | IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO | | THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS | | PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER | | CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE | | TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH | | SECTION 553.86, FLORIDA STATUTES. |
|