Plan Review Notes
Plan Review Notes For Permit 16081096
Permit Number 16081096
Review Stop M
Sequence Number 1
Notes
Date Text
2016-09-06 15:17:291ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16081096
 9/6/16
  
 1) THE PROJECT IS INCORRECTLY IDENTIFED AS A RENOVATION
 IN THE PROJECT SUMMARY OF THE ENERGYGAUGE COMPLIANCE
 SUBMITTAL. THE CORRECT IDENTIFICATION PER SECTION 202
 FBC-14 EXISTING BUILDING IS CHANGE OF OCCUPANCY- PLEASE
 CORRECT.
  
 2) THE SUMMARY AC CALCULATIONS MUST INCLUDE THE TOTAL
 LATENT GAINS FOR EACH SYSTEM- REFER TO SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION EXCEPTION.
  
 3) SHEET M0.2: RTU-1 & RTU- 3A AT 12.5 AND 5TON PER THE
 SCHEDULE ARE EACH EXCEEDING THE COOLING LOADS
 CALCULATED- SEE SECTION C403.2.2.
  
 4) M0.2: THE ELECTRIC HEAT KW CAPACITIES SHOWN IN THE
 SCHEDULE FOR RTU-1 AND RTU-3B ARE UNDERSIZED PER THE
 CALCULATED HEATING LOADS- C403.2.2.
  
 5) M0.2: PLEASE PROVIDE THE COOLING CAPACITY AND
 EFFICIENCY RATING OF RTU-4 IN THE SCHEDULE- SEE PAGE 6
 OF ENERGY SUBMITTAL.
  
 6) M0.2: THE O/A CALCULATIONS FOR THE SQUASH COURTS AND
 SPECTATOR AREA ARE NOT IN COMPLIANCE WITH TABLE 403.3
 FBC-14 MECHANICAL- RATES AND OCCUPANT DENSITIES.
  
 7) REFER TO SECTION C403.2.4.4 AND SHOW COMPLIANCE FOR
 O/A SHUTOFF DAMPER CONTROLS.
  
 8) PROVIDE CONTROL DIAGRAMS FOR EXHAUST FANS F-1A &
 F-1B.
  
 9) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF RTU'S 3A & 3B PER SECTION 606.2.1. NOTE:
 THIS REQJUIREMENT WILL BE WAIVED PENDING SUBMITTAL OF
 MANUFACTURER'S DATA INDICATING THE SYSTEMS CANNOT
 EXCEED 2000 CFMS OF SUPPLY AIR.
  
 10) M1.1: THE RETURN AIR GRILLS FOR RTU'S 3A & 3B ARE
 UNDERSIZED FOR 1272 CMFS OF RETURN AIR.
  
 11) PLEASE CLARIFY THE USE OF THE OPEN AREA. THE TYPE
 OF ACTIVITIES THAT WILL TAKE PLACE THERE COULD IMPACT
 THE O/A RATES AND AC SYSTEMS.
  
 12) PROVIDE A MECHANICAL ROOF PLAN SHOWING RTU AND FAN
 LOCATIONS, AND ALL REQUIRED CLEARANCE DISTANCE
 MEASUREMENTS.
  
 13) PROVIDE THE WIND LOAD DESIGN CRITERIA FOR ALL
 ROOFTOP MECHANICAL INSTALLATIONS, AND DRAWINGS AND
 DETAILS FOR COMPLETE INSTALLATIONS OF THE RTU'S AND
 CURBS, FANS AND CURBS, AND ROOFTOP DUCTWORK.
  
 14) REFER TO SECTION 6.4.3 OF THE ASHRAE STANDARD 90.1
 AND PROVIDE HVAC CONTROL NOTES ON SHEET M6.1.
  