2016-08-29 17:10:04 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: 1250 ELIZABETH AVENUE |
| JOB ADDRESS: 1250 ELIZABETH AVENUE |
| DESCRIPTION: SQUASH COURTS, WAREHOUSE, |
| OFFICE-RENOVATING EXISTING SPACE |
| MASTER PERMIT: 16081096 |
| |
| BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| SUBMITTED CORRECTIONS. |
| |
| 1. IN YOUR GENERAL ELECTRICAL NOTES ON SHEET E0.1, YOUR |
| NOTE 2 SHALL QUOTE THE SPECIFIC APPLICABLE CODES AND |
| NOT GENERALIZATION. NOTE 3 DICTATES CONDUCTOR |
| INSULATION BASED ON SIZE. CONDUCTOR INSULATION IS |
| DETERMINED BY THE APPLICATION AND NOT SIZE. A |
| CONDUCTOR, NO MATTER WHAT SIZE IN A WET LOCATION SHALL |
| BE INSULATED ACCORDINGLY. |
| 2. NEC 230.2(E) REQUIRES THAT EACH SERVICE BE PLACARDED |
| TO INDICATE THE EXISTENCE AND LOCATION OF ANY OTHER |
| SERVICE SUPPLYING THE BUILDING. |
| 3. NEC 600.5 STATES THAT EACH COMMERCIAL BUILDING AND |
| EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED |
| OUTLET IN AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO |
| EACH TENANT SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE |
| HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED |
| ACCESSIBLE TO PEDESTRIANS. I DO NOT SEE THIS ON ANY OF |
| THE DOORS ON EITHER THE POWER OR LIGHTING PLAN. |
| 4. NEC 210.62 CALLS FOR AT LEAST ONE RECEPTACLE OUTLET |
| TO BE INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW |
| FOR EVERY 12 LINEAR FT. OR MAJOR PORTION THEREOF AREA |
| MEASURED HORIZONTALLY. THIS APPLIES TO THE STORE FRONT |
| AREAS OF THIS BLDG. |
| 5. NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20 |
| AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET |
| LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF |
| WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL |
| 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING |
| RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE |
| ?WR?. CORRECT DETAIL 3 ON SHEET E5.1 TO COMPLY. ( |
| REQUIRES AN IN-USE TYPE COVER). |
| 6. FBC-B 1006.3 REQUIRES THAT THE EXIT DISCHARGE BE |
| ILLUMINATED UNDER EMERGENCY POWER. THE SUBMITTED |
| DRAWINGS DO SHOW EXTERIOR LIGHTING BUT NOT ANY |
| EMERGENCY LIGHTING. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |
| |