2016-08-26 05:16:41 | 1) THE MANUFACTURER'S SPECIFICATION SHEETS FOR THE GAS |
| DRYER AND THE GAS RANGE DO NOT SHOW THAT THE APPLIANCES |
| ARE LISTED AND LABELED IN ACCORDANCE WITH THE 2014 FUEL |
| GAS CODE SEC. 301.3. SUBMIT TWO CCOPIES OF |
| SPECIFICATIONS THAT SHOW COMPLIANCE. |
| 2) THE GAS RISER DIAGRAM THAT HAS BEEN SUBMITTED LACKS |
| NECESSARY INFORMATION FOR A PROPER AND COMPREHENSIVE |
| PLAN REVIEW. COMPLY WITH ALL OF THE FOLLOWING |
| REQUIREMENTS AND SUBMIT ALL REQUIRED INFORMATION |
| SHOWING COMPLIANCE. |
| 3) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. |
| G2413. |
| 4) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8 |
| THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR |
| 2014 FBC-RES. SEC. G2413. |
| 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, ( GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014 |
| FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G |
| 2413.3. |
| 6) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE |
| DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE |
| THAT WERE USED IN THE DESIGN OF THIS SYSTEM. FGC |
| SEC.402.3. THE CODE EDITION THAT IS REFERENCED ON THE |
| GAS DRAWING IS OUTDATED. THE GAS CODE THAT IS IN EFFECT |
| IS THE FIFTH EDITION ( THE 2014) OF THE FBC. |
| 7) SHOW THE SIZE OF THE LINE ON THE OUTLET OF THE GAS |
| METER.THIS LINE SHALL BE SIZED FOR THE TOTAL BTU LOAD |
| ON THE SYSTEM AND THE TOTAL DEVELOPED LENGTH FROM THE |
| METER TO THE MOST REMOTE OUTLET ON THE SYSTEM.2014 FGC |
| SEC. 402.4.1. |
| 8) THE GAS PLAN SHOWS WHAT APPEARS TO BE WATER LINES |
| CONNECTED TO THE GAS LINES. THE NOTE STATES " TO |
| EXISTING H.W. LINES". CLARIFY. |
| 9) THE BTU LOAD OF THE EXISTING GAS WATER HEATER THAT |
| IS BEING REPLACED MUST BE ADDED INTO THE TOTAL BTU LOAD |
| ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY |
| SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST BE |
| REDONE TO ENSURE A SAFE OPERATING SYSTEM. FGC SECS. |
| 401.4, 401.8, 402.1,402.2, 402.3 |
| 10) SHOW THE DISTANCE OF THE TANKLESS WATER HEATER TO |
| THE WIDOW. THE TANKLESS WATER HEATER SHALL BE LOCATED |
| IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS FROM BUILDING OPENINGS INCLUDING SOFFIT |
| VENTS. |
| 11) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| DRYER AND THE WATER HEATER IN THE UTILITY ROOM PER THE |
| 2014 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. |
| G 2407. |
| 12) THE SCOPE OF WORK SHOWN ON THE PLANS EXCEEDS THE |
| SCOPE OF WORK DESCRIBED ON THE APPLICATION.REVISE THE |
| DESCRIPTION OF WORK ON THE APPLICATION TO CORRELATE |
| WITH ALL WORK SHOWN ON THE PLANS. WPB AMEND. TO 2014 |
| FBC SEC.107.2.1. |
| 13) THE VALUE OF THIS PROJECT SHOWN ON THE APPLICATION |
| APPEARS LOW. SUBMIT A DETAILED, QUANTITY ESTIMATE OR A |
| BONA FIDE SIGNED CONTRACT IN ACCCORDANCE WITH WPB |
| AMEND. TO FBC SEC.109.3. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |