Plan Review Notes
Plan Review Notes For Permit 16081065
Permit Number 16081065
Review Stop G
Sequence Number 1
Notes
Date Text
2016-08-26 05:16:411) THE MANUFACTURER'S SPECIFICATION SHEETS FOR THE GAS
 DRYER AND THE GAS RANGE DO NOT SHOW THAT THE APPLIANCES
 ARE LISTED AND LABELED IN ACCORDANCE WITH THE 2014 FUEL
 GAS CODE SEC. 301.3. SUBMIT TWO CCOPIES OF
 SPECIFICATIONS THAT SHOW COMPLIANCE.
 2) THE GAS RISER DIAGRAM THAT HAS BEEN SUBMITTED LACKS
 NECESSARY INFORMATION FOR A PROPER AND COMPREHENSIVE
 PLAN REVIEW. COMPLY WITH ALL OF THE FOLLOWING
 REQUIREMENTS AND SUBMIT ALL REQUIRED INFORMATION
 SHOWING COMPLIANCE.
 3) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
 4) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8
 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2014 FBC-RES. SEC. G2413.
 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, ( GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
 6) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE
 THAT WERE USED IN THE DESIGN OF THIS SYSTEM. FGC
 SEC.402.3. THE CODE EDITION THAT IS REFERENCED ON THE
 GAS DRAWING IS OUTDATED. THE GAS CODE THAT IS IN EFFECT
 IS THE FIFTH EDITION ( THE 2014) OF THE FBC.
 7) SHOW THE SIZE OF THE LINE ON THE OUTLET OF THE GAS
 METER.THIS LINE SHALL BE SIZED FOR THE TOTAL BTU LOAD
 ON THE SYSTEM AND THE TOTAL DEVELOPED LENGTH FROM THE
 METER TO THE MOST REMOTE OUTLET ON THE SYSTEM.2014 FGC
 SEC. 402.4.1.
 8) THE GAS PLAN SHOWS WHAT APPEARS TO BE WATER LINES
 CONNECTED TO THE GAS LINES. THE NOTE STATES " TO
 EXISTING H.W. LINES". CLARIFY.
 9) THE BTU LOAD OF THE EXISTING GAS WATER HEATER THAT
 IS BEING REPLACED MUST BE ADDED INTO THE TOTAL BTU LOAD
 ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY
 SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST BE
 REDONE TO ENSURE A SAFE OPERATING SYSTEM. FGC SECS.
 401.4, 401.8, 402.1,402.2, 402.3
 10) SHOW THE DISTANCE OF THE TANKLESS WATER HEATER TO
 THE WIDOW. THE TANKLESS WATER HEATER SHALL BE LOCATED
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FROM BUILDING OPENINGS INCLUDING SOFFIT
 VENTS.
 11) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 DRYER AND THE WATER HEATER IN THE UTILITY ROOM PER THE
 2014 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC.
 G 2407.
 12) THE SCOPE OF WORK SHOWN ON THE PLANS EXCEEDS THE
 SCOPE OF WORK DESCRIBED ON THE APPLICATION.REVISE THE
 DESCRIPTION OF WORK ON THE APPLICATION TO CORRELATE
 WITH ALL WORK SHOWN ON THE PLANS. WPB AMEND. TO 2014
 FBC SEC.107.2.1.
 13) THE VALUE OF THIS PROJECT SHOWN ON THE APPLICATION
 APPEARS LOW. SUBMIT A DETAILED, QUANTITY ESTIMATE OR A
 BONA FIDE SIGNED CONTRACT IN ACCCORDANCE WITH WPB
 AMEND. TO FBC SEC.109.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  