Notes |
Date |
Text |
2016-08-31 16:04:58 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | 1] CLARIFY IF THE GENERATOR IS EQUIPPED WITH AN | | INTERGAL DISCONNECT OR IS IT WITHIN SIGHT. NEC 445.18 | | | | 2] PROVIDE MANUFACTURE SPECS OF THE TRANSFER-SWITCH TO | | VERIFY IF ITS A SEPERATELY OR NON-SEPERATELY DERIVED | | SYSTEM. FBC 107 |
|