2016-11-03 10:45:42 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16081034 | | 11/3/16 | | | | 1) THE O/A INTAKES MUST MEET THE PROVISIONS FOR | | EXTERIOR WALL OPENING PROTECTIVES IN ACCORDANCE WITH | | FBC-14 BUILDING- SEE SECTION 401.5 FBC-14 MECHANICAL | | AND 1609 FBC-14 BUILDING. IF USING LOUVERS, PROVIDE A | | FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA, AND PROVIDE | | DOUMENTATION OF COMPLIANCE WITH AMCA 550. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|