Plan Review Notes
Plan Review Notes For Permit 16081034
Permit Number 16081034
Review Stop E
Sequence Number 2
Notes
Date Text
2016-11-02 17:48:352ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 PREVIOUS COMMENT NOT ADDRESSED:
  
 8. PER NEC 220.87 PROVIDE 1 YEAR MAXIMUM DEMAND DATA
 REPORT TO VERIFY IF EXISTING SERVICE IS SUFFICIENT TO
 CARRY NEW SERVICE ADDED.
 COMMENTS:
  
 1. LABEL ALL MAINS 1OF5, 2OF5 ETC. NEC 230.71
 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 3. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
2016-08-30 14:00:56ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: OLAOLU REAL ESTATE
 JOB ADDRESS: 2580 METRO CENTRE BLVD.
 DESCRIPTION: INTERIOR RENOVATION
 MASTER PERMIT: 16081034
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. NEC 600.5 STATES THAT EACH COMMERCIAL BUILDING AND
 EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED
 OUTLET IN AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO
 EACH TENANT SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE
 HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED
 ACCESSIBLE TO PEDESTRIANS. I DO NOT SEE THIS ON ANY OF
 THE DOORS ON EITHER THE POWER OR LIGHTING PLAN.
 2. NEC 210.62 CALLS FOR AT LEAST ONE RECEPTACLE OUTLET
 TO BE INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW
 FOR EVERY 12 LINEAR FT. OR MAJOR PORTION THEREOF AREA
 MEASURED HORIZONTALLY. THIS APPLIES TO THE STORE FRONT
 AREAS OF THIS BLDG.
 3. ROOMS 136, 142, 145, 150, 158, 159, 160 & 161 SHALL
 COMPLY WITH NEC 517 PART III.
 4. AUTOMATIC CONTROL FOR RECEPTACLES AS INDICATED IN
 FBC-E 405.7.1 IS REQUIRED.
 5. DISCONNECTS CONFORMING WITH NEC 440.12 IS REQUIRED
 FOR THE CONDENSING UNITS.
 6. NEC 314.27(D): BOXES USED FOR THE SOLE SUPPORT OF
 CEILING FANS SHALL BE MARKED BY THE MANUFACTURER AS
 SUITABLE FOR THE PURPOSE, AND INDICATE THE WEIGHT
 LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT PADDLE
 FANS HEAVIER THAN 70 LBS.
 7. EMERGENCY LIGHTING IS REQUIRED FOR THE ROOMS
 MENTIONED ABOVE IN COMMENT #3.
 8. PROVIDE MAXIMUM DEMAND DATA FOR 1 YEAR AS REQUIRED
 BY NEC 220.87 TO DETERMINE THAT THE EXISTING SERVICE IS
 CAPABLE OF ABSORBING THE ADDED DEMAND.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY
 .
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  