2016-11-02 17:48:35 | 2ND ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 |
| PREVIOUS COMMENT NOT ADDRESSED: |
| |
| 8. PER NEC 220.87 PROVIDE 1 YEAR MAXIMUM DEMAND DATA |
| REPORT TO VERIFY IF EXISTING SERVICE IS SUFFICIENT TO |
| CARRY NEW SERVICE ADDED. |
| COMMENTS: |
| |
| 1. LABEL ALL MAINS 1OF5, 2OF5 ETC. NEC 230.71 |
| 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| VERBIAGE IN CODE. |
| 3. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| TO CONTACT ME SHOULD YOU HAVE ANY |
| |
| |
| VALENTINO PEREZ |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6717 |
| [email protected] |
| |
2016-08-30 14:00:56 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: OLAOLU REAL ESTATE |
| JOB ADDRESS: 2580 METRO CENTRE BLVD. |
| DESCRIPTION: INTERIOR RENOVATION |
| MASTER PERMIT: 16081034 |
| |
| BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| SUBMITTED CORRECTIONS. |
| |
| 1. NEC 600.5 STATES THAT EACH COMMERCIAL BUILDING AND |
| EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED |
| OUTLET IN AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO |
| EACH TENANT SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE |
| HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED |
| ACCESSIBLE TO PEDESTRIANS. I DO NOT SEE THIS ON ANY OF |
| THE DOORS ON EITHER THE POWER OR LIGHTING PLAN. |
| 2. NEC 210.62 CALLS FOR AT LEAST ONE RECEPTACLE OUTLET |
| TO BE INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW |
| FOR EVERY 12 LINEAR FT. OR MAJOR PORTION THEREOF AREA |
| MEASURED HORIZONTALLY. THIS APPLIES TO THE STORE FRONT |
| AREAS OF THIS BLDG. |
| 3. ROOMS 136, 142, 145, 150, 158, 159, 160 & 161 SHALL |
| COMPLY WITH NEC 517 PART III. |
| 4. AUTOMATIC CONTROL FOR RECEPTACLES AS INDICATED IN |
| FBC-E 405.7.1 IS REQUIRED. |
| 5. DISCONNECTS CONFORMING WITH NEC 440.12 IS REQUIRED |
| FOR THE CONDENSING UNITS. |
| 6. NEC 314.27(D): BOXES USED FOR THE SOLE SUPPORT OF |
| CEILING FANS SHALL BE MARKED BY THE MANUFACTURER AS |
| SUITABLE FOR THE PURPOSE, AND INDICATE THE WEIGHT |
| LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT PADDLE |
| FANS HEAVIER THAN 70 LBS. |
| 7. EMERGENCY LIGHTING IS REQUIRED FOR THE ROOMS |
| MENTIONED ABOVE IN COMMENT #3. |
| 8. PROVIDE MAXIMUM DEMAND DATA FOR 1 YEAR AS REQUIRED |
| BY NEC 220.87 TO DETERMINE THAT THE EXISTING SERVICE IS |
| CAPABLE OF ABSORBING THE ADDED DEMAND. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |