Plan Review Notes
Plan Review Notes For Permit 16081034
Permit Number 16081034
Review Stop M
Sequence Number 1
Notes
Date Text
2016-08-30 16:38:321ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16081034
 8/30/16
  
 1) THE SELECTED AC SYSTEMS ARE OVERSIZED IN COOLING AND
 HEATING CAPACITIES PER THE SUBMITTED WHOLE AREA
 CALCULATION- REFER TO SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION.
  
 2) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF AHU'S #1-6 PER SECTION 606.2.1. THIS
 REQUIREMENT MAY BE WAIVED IF MANUFACTURER'S
 SPECIFICATIONS INDICATE THE UNITS DO NOT HAVE THE
 CAPACITY TO PRODUCE OVER 2000 CFMS EACH.
  
 3) EXHAUST VENTILATION IS REQUIRED FOR THE LAB AND
 RECIRCULATION OF THE AIR IS PROHIBITED EXCEPT WHERE THE
 RESULTING AIR STREAM CONSISTS OF NOT MORE THAN 10% AIR
 RECIRCULATED FROM THE SPACE- SEE TABLE 403.3 AND
 FOOTNOTE G.
  
 4 ) REFER TO TABLE 403.3 AND PROVIDE COMPLETE
 VENTILATION CALCULATIONS FOR THE PROPOSED OCCUPANCY
 INCLUDING THE EXAM ROOMS, THE INFUSION ROOM, THE LAB,
 THE PHARMACY, THE STORAGE ROOMS, AND CORRIDORS.
  
 5) PROVIDE CONDENSATE DISPOSAL DETAILS FOR AHU #5.
  
 6) PROVIDE EQUIPMENT SCHEDULES FOR THE MOTORIZED
 DAMPERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved