Plan Review Notes
Plan Review Notes For Permit 16081034
Permit Number 16081034
Review Stop B
Sequence Number 1
Notes
Date Text
2016-09-12 14:35:38BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16081034
 ADD: 2580 METROCENTRE BLVD. SUITE 3, 4 & 5
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: 753-7400
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 1) WITHIN THE SET OF PLANS THERE IS NO PLAN WITH
 PROJECT INFORMATION, CODE ANALYSIS AND LIFE SAFETY
 PLAN.
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1:
  
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS/ 107.3.5.1.1 BUILDING:
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503). PROVIDE SQUARE FOOTAGE OF BUILDING.
 FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE
 THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 FIRE SUPPRESSION SYSTEMS REQUIRED? YES OR NO, THEY
 SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS/ PRE-ENGINEERED SYSTEMS
 LIFE SAFETY PLAN SHALL INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE ACCESS CODE
 SIGNS SHALL BE PROVIDED IN ACCORDANCE WITH 216 AND
 SHALL COMPLY WITH 703.
  
 2) SINCE THERE IS NO CODE INFORMATION PROVIDED NO LIFE
 SAFETY PLAN FOR WHICH WAY THE OCCUPANTS WILL BE
 TRAVELING TO REACH AN EXIT NOR THE QUANTITY OF
 OCCUPANTS EACH CORRIDOR WILL BE HANDLING COMPLIANCE
 CANNOT BE DETERMINED FOR 2014 FBC-B TABLE 1018.1
 BUSINESS CORRIDORS WITH AN OCCUPANT LOAD GREATER THAN
 30 IN A NON-SPRINKLERED BUILDING WOULD REQUIRE 1 HOUR
 FIRE RATED CORRIDORS AND OPENING PROTECTIVES IN
 ACCORDANCE WITH FBC-B TABLE 716.5.
 3) SHEET A-1 SHOWS THE TENANT SPACE IS APPROXIMATELY
 8,500 SQUARE FEET IN AREA AND APPEARS TO BE A MIXED USE
 OCCUPANCY BETWEEN A BUSINESS AND A2/A3 ASSEMBLY
 OCCUPANCY OF APPROXIMATELY 1,150 SQ. FT. WHICH IS OVER
 10 % OF THE TENANT FLOOR AREA. THE DESIGNER OF RECORD
 WILL NEED TO IDENTIFY HOW THE MIXED USE OCCUPANCY IS
 GOING TO BE CLASSIFIED? AS SEPARATED UNDER 508.3.3 OR
 NONSEPARATED OCCUPANCIES UNDER 508.3.
  
 4) THERE ARE NO SECTIONS FOUND ON SHEET A1 FOR AN
 ACCESSIBLE FRONT OFFICE CHECK IN NOR ANY FOR CHECKING
 OUT. FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. 904.3.3 CHECK WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3.
  
 5A) SHEET A1 THE STAFF SHOWER IN THE BATHROOM 118
 MEASURES 38 X38 INCHES. PLEASE PROVIDE COMPLIANCE WITH
 THE ACCESS. CODE FOR THE REQUIRED SIZE 36 X 36 INCHES
 SEE 608.2.
  
 5B) THE PLAN DOES NOT SHOW THE CONTROL VALVE WALL NOR
 THE SEAT WALL NOR REQUIRED CLEARANCES. SEE ACCESS. CODE
 608.2.1 AND FIGURE 608.2.1. PLEASE ALSO PROVIDE
 COMPLIANCE FOR GRAB BAR PLACEMENT SEE SECTION 608.3 AND
 FIGURE 608.3.1 AND CONTROLS FIGURE 608.5.1.
  
 6) SHEET A1 WILL ALSO NEED TO SHOW COMPLIANCE FOR THE A
 SHOWER IN THE BATHROOM 113 FOR A STANDARD ROLL IN
 SHOWER IN COMPLIANCE WITH 608.3.2, & 608.6.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  