2016-09-12 14:35:38 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16081034 |
| ADD: 2580 METROCENTRE BLVD. SUITE 3, 4 & 5 |
| CONT: ANDERSON MOORE CONSTRUCTION |
| TEL: 753-7400 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: |
| ACTION: DENIED |
| |
| 1) WITHIN THE SET OF PLANS THERE IS NO PLAN WITH |
| PROJECT INFORMATION, CODE ANALYSIS AND LIFE SAFETY |
| PLAN. |
| 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1: |
| |
| ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS/ 107.3.5.1.1 BUILDING: |
| OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| TABLE 503). PROVIDE SQUARE FOOTAGE OF BUILDING. |
| FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE |
| THE FOLLOWING COMPONENTS: |
| FIRE-RESISTANT SEPARATIONS |
| FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| FIRE SUPPRESSION SYSTEMS REQUIRED? YES OR NO, THEY |
| SHALL INCLUDE: |
| SCHEMATIC FIRE SPRINKLERS/ PRE-ENGINEERED SYSTEMS |
| LIFE SAFETY PLAN SHALL INCLUDE THE FOLLOWING |
| REQUIREMENTS: |
| OCCUPANT LOAD AND EGRESS CAPACITIES |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| DOORS |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| ACCESSIBILITY REQUIREMENTS SHALL INCLUDE ACCESS CODE |
| SIGNS SHALL BE PROVIDED IN ACCORDANCE WITH 216 AND |
| SHALL COMPLY WITH 703. |
| |
| 2) SINCE THERE IS NO CODE INFORMATION PROVIDED NO LIFE |
| SAFETY PLAN FOR WHICH WAY THE OCCUPANTS WILL BE |
| TRAVELING TO REACH AN EXIT NOR THE QUANTITY OF |
| OCCUPANTS EACH CORRIDOR WILL BE HANDLING COMPLIANCE |
| CANNOT BE DETERMINED FOR 2014 FBC-B TABLE 1018.1 |
| BUSINESS CORRIDORS WITH AN OCCUPANT LOAD GREATER THAN |
| 30 IN A NON-SPRINKLERED BUILDING WOULD REQUIRE 1 HOUR |
| FIRE RATED CORRIDORS AND OPENING PROTECTIVES IN |
| ACCORDANCE WITH FBC-B TABLE 716.5. |
| 3) SHEET A-1 SHOWS THE TENANT SPACE IS APPROXIMATELY |
| 8,500 SQUARE FEET IN AREA AND APPEARS TO BE A MIXED USE |
| OCCUPANCY BETWEEN A BUSINESS AND A2/A3 ASSEMBLY |
| OCCUPANCY OF APPROXIMATELY 1,150 SQ. FT. WHICH IS OVER |
| 10 % OF THE TENANT FLOOR AREA. THE DESIGNER OF RECORD |
| WILL NEED TO IDENTIFY HOW THE MIXED USE OCCUPANCY IS |
| GOING TO BE CLASSIFIED? AS SEPARATED UNDER 508.3.3 OR |
| NONSEPARATED OCCUPANCIES UNDER 508.3. |
| |
| 4) THERE ARE NO SECTIONS FOUND ON SHEET A1 FOR AN |
| ACCESSIBLE FRONT OFFICE CHECK IN NOR ANY FOR CHECKING |
| OUT. FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF WORK |
| SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 |
| INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. 904.3.3 CHECK WRITING SURFACES. |
| WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY |
| WITH 902.3. |
| |
| 5A) SHEET A1 THE STAFF SHOWER IN THE BATHROOM 118 |
| MEASURES 38 X38 INCHES. PLEASE PROVIDE COMPLIANCE WITH |
| THE ACCESS. CODE FOR THE REQUIRED SIZE 36 X 36 INCHES |
| SEE 608.2. |
| |
| 5B) THE PLAN DOES NOT SHOW THE CONTROL VALVE WALL NOR |
| THE SEAT WALL NOR REQUIRED CLEARANCES. SEE ACCESS. CODE |
| 608.2.1 AND FIGURE 608.2.1. PLEASE ALSO PROVIDE |
| COMPLIANCE FOR GRAB BAR PLACEMENT SEE SECTION 608.3 AND |
| FIGURE 608.3.1 AND CONTROLS FIGURE 608.5.1. |
| |
| 6) SHEET A1 WILL ALSO NEED TO SHOW COMPLIANCE FOR THE A |
| SHOWER IN THE BATHROOM 113 FOR A STANDARD ROLL IN |
| SHOWER IN COMPLIANCE WITH 608.3.2, & 608.6. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |