Plan Review Notes
Plan Review Notes For Permit 16081032
Permit Number 16081032
Review Stop P
Sequence Number 1
Notes
Date Text
2016-08-26 05:42:371) THIS PLUMBING WORK CANNOT BE DONE BY A GENERAL
 CONTRACTOR AS THIS CONTRACTOR DOES NOT HOLD A PLUMBING
 LICENSE. SUBMIT AN APPLICATION BY AN ACTIVELY LICENSED
 AND INSURED PLUMBING CONTRACTOR IN ACCORDANCE WITH FL.
 STATUTE 489.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 HEATER. WHAT IS THE CAPACITY IN GALLONS? IS THIS AN
 EXACT REPLACEMENT OF THE EXISTING OR IS THE GALLON
 CAAPACITY INCREASING? IF THE GALLON CAPACITY IS
 INCREASING ALONG THE WITH THE ELEMENT RATING OF THE
 HEATER THEN THE ELECTRIC SUPPLY TO THE HEATER MAY HAVE
 TO BE MODIFIED. IF THIS IS AN EXACT REPLACEMENT, THEN
 INDICATE SUCH ON THE PLAN AND INCLUDE THE OTHER
 REQUIRED INFO. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  