Plan Review Notes
Plan Review Notes For Permit 16081029
Permit Number 16081029
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-31 11:15:52REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - PASSED WITH THE FOLLOWING PROVISO'S
  
 1] ALL MAINS MUST BE GROUPED IN ACCORDANCE WITH NEC
 230.72
  
 2] PROVIDE AN INTERSYSTEM BONDING TERMINAL PER NEC
 250.94