| 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. |
| G2413. |
| 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| DRYER, TANKLESS WATER HEATERS, STOVE AND FIREPLACE PER |
| THE 2014 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. |
| SEC. G 2407. |
| 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| 4) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE |
| WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. |
| 5) SUBMIT COPIES OF THE SIZING TABLES BEING USED TO |
| DESIGN THE SYSTEM OR REFERENCE THE SPECIFIC TABLES ON |
| THE PLANS. A REVIEW COULD NOT BE DONE ON THE PIPNG |
| SYSTEM DUE TO THE LACK OF THIS INFORMATION. |
| 6) SHOW THE MEASUREMENT (LENGTH) OF THE PIPING FROM THE |
| SECOND STAGE REGULATOR TO THE APPLIANCE.2014 FGC SEC. |
| 402.4.1. |
| 7) SUBMIT MANUF. SPECIFICATIONS FOR THE SECOND STAGE |
| REGULATORS. HOW WILL THEY BE VENTED? |
| 8) SUPPLY THE CORRESPONDING EHD FOR EACH SIZE THE |
| WARDFLEX PIPE.FBC SEC. 107.2.1. |
| 9) THE FUTURE OUTLET FOR THE FIREPLACE SHALL BE VALVED |
| AND CAPPED. |
| |