Plan Review Notes
Plan Review Notes For Permit 16080974
Permit Number 16080974
Review Stop M
Sequence Number 4
Notes
Date Text
2016-11-29 11:56:122ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16080974
 11/29/16
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS. I HAVE
 REPRINTED BELOW.
  
 1ST REVIEW COMMENT #1: IF CHOOSING NOT TO PROVIDE
 CONDITIONED MAKEUP AIR, PLEASE PROVIDE AN AC
 CALCULATION THAT INCORPORATES THE ADDITIONAL HEAT LOAD
 FROM THE MAKEUP AIR. THE CALCULATION MUST INDICATE THAT
 THE EXISTING SYSTEM CAN HANDLE THE ADDITINAL LOAD.
 PLEASE SEE SECTION R302.1 FBC-14 ENERGY CONSERVATION
 FOR INTERIOR DESIGN TEMPERATURE (75 DEGREES F FOR
 COOLING).
  
 THE SUBMITTED CALCULATION INDICATES AN INTERIOR DESIGN
 DRYBULB TEMPERATURE OF 75 DEGREES. THE ENGINEER HAS
 WRITTEN IN HIS REPONSE NARRATIVE THAT THE TEMPERATURE
 WILL BE SET AT 81 DEGREES IN THE KITCHEN AREA, HOWEVER
 THERE IS ONE AC SYSTEM THAT IS PROVIDING COOLING TO
 BOTH THE DINING AND KITCHEN AREAS. PROVIDE EVIDENCE ON
 THE PLAN THAT THE INTERIOR DESIGN TEMPERATURE IN THE
  
 KITCHEN WILL BE 81 DEGREES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  