Plan Review Notes For Permit 16080974 |
Permit Number |
16080974 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2016-11-29 11:56:12 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16080974 | | 11/29/16 | | | | 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS. I HAVE | | REPRINTED BELOW. | | | | 1ST REVIEW COMMENT #1: IF CHOOSING NOT TO PROVIDE | | CONDITIONED MAKEUP AIR, PLEASE PROVIDE AN AC | | CALCULATION THAT INCORPORATES THE ADDITIONAL HEAT LOAD | | FROM THE MAKEUP AIR. THE CALCULATION MUST INDICATE THAT | | THE EXISTING SYSTEM CAN HANDLE THE ADDITINAL LOAD. | | PLEASE SEE SECTION R302.1 FBC-14 ENERGY CONSERVATION | | FOR INTERIOR DESIGN TEMPERATURE (75 DEGREES F FOR | | COOLING). | | | | THE SUBMITTED CALCULATION INDICATES AN INTERIOR DESIGN | | DRYBULB TEMPERATURE OF 75 DEGREES. THE ENGINEER HAS | | WRITTEN IN HIS REPONSE NARRATIVE THAT THE TEMPERATURE | | WILL BE SET AT 81 DEGREES IN THE KITCHEN AREA, HOWEVER | | THERE IS ONE AC SYSTEM THAT IS PROVIDING COOLING TO | | BOTH THE DINING AND KITCHEN AREAS. PROVIDE EVIDENCE ON | | THE PLAN THAT THE INTERIOR DESIGN TEMPERATURE IN THE | | | | KITCHEN WILL BE 81 DEGREES. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|